Grow tent exhaust fan CFM calculator
Estimate required grow tent or greenhouse airflow in CFM and m³/h with carbon filter, duct length, elbow and air-exchange adjustments.
Inputs
Results
Estimated free-air rating
60 air changes/hour · 64.3% modeled airflow retained
- Room volume
- 104 ft³
- Room volume
- 2.94 m³
- Target delivered airflow
- 104 CFM
- Target delivered airflow
- 176.7 m³/h
- Estimated free-air rating
- 161.7 CFM
- Estimated free-air rating
- 274.8 m³/h
Delivered flow and fan rating
Compare required delivery with the estimated no-restriction rating.
Inputs used
- Interior length
- 4 ft
- Interior width
- 4 ft
- Interior height
- 6.5 ft
- Time per air exchange
- 1 min
- Carbon filter loss
- 25 %
- Straight duct run
- 10 ft
- Duct loss per reference length
- 5 % / 10 ft
- 90° elbows
- 2
- Loss per elbow
- 5 %
Worked calculation
- Measure interior air volume
4 ft × 4 ft × 6.5 ft = 104 ft³
- Find the delivered airflow needed
104 ft³ ÷ 1 min = 104 CFM
- Multiply retained fractions
0.75 filter × 0.95 duct × 0.9025 elbows = 64.3% retained
- Find the estimated free-air rating
104 CFM ÷ 0.64303 = 161.73 CFM (274.8 m³/h)
How the model works
Filter, duct and elbow inputs are planning allowances. Duct loss compounds over each 10 ft equivalent, and elbow loss compounds for each fitting. Pressure drop depends on airflow, duct diameter, filter loading and fitting geometry.
Select a fan using its CFM at the operating static pressure for your system. Use the estimated free-air rating as a screening number. Check intake area, ventilation demand from heat and moisture, and the installed fan curve.
References
Common questions
Why divide by remaining airflow when sizing an exhaust fan?
A fan retaining 75% of rated flow must start with at least 100 ÷ 0.75 = 133.3 CFM to deliver 100 CFM under that assumed restriction.
What is the difference between free air and delivered CFM?
Free-air CFM is a no-restriction rating. Delivered CFM is the installed flow after pressure from filters, fittings, ducts and the inlet.