Manufacturing high-bay LPD
Apply the 25 to 50 ft manufacturing high-bay category to a plant floor using high-output LED fixtures.
Inputs
View results ↑- Actual LPD
- 0.814W/ft²
- LPD margin
- 34.4%
- Energy saved
- 93,947kWh/yr
- Payback
- 3.5yr
Installed power and allowance
Edit inputs ↓Connected LPD screen
Within screen- Connected power density0.81 / ≤ 1.24 W/ft² within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Additional readings
| Selected LPD allowance | 1.24W/ft² |
|---|---|
| Connected load | 19,536W |
| Connected power allowance | 29,760W |
| Allowance minus connected load | 10,224W |
| Equivalent controlled load | 17,582.4W |
| Legacy lighting energy | 188,892kWh/yr |
| Post-retrofit lighting energy | 94,944.96kWh/yr |
| Annual utility savings | 10,334.17USD/yr |
Worked calculation
US customary results for the original preset.
- Divide 19536 W of connected load by 24000 ft² to get 0.814 W/ft². The selected limit is 1.24 W/ft².
- After applying the control credit to annual use, compare 1.9e+5 kWh/yr before retrofit with 94945 kWh/yr after retrofit.
- At 0.11 USD/kWh, the annual cost difference is 10334.17 USD/yr. Simple payback is 3.48 yr.
Calculation method
Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.
- Connected lighting power density
- LPD = fixture count × input watts/floor area
- Annual energy savings
- ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
- Simple payback
- Years = retrofit cost/(ΔkWh × utility rate), when savings are positive
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.
Sources and assumptions ↗Manufacturing high-bay LPD
Inputs
| Space type | Manufacturing · high-bay |
|---|---|
| Lighted floor area | 24,000ft² |
| Fixture count | 132 |
| Installed watts per fixture | 148W |
| Control energy credit | 10% |
| Operating hours | 5,400h/yr |
| Legacy watts per fixture | 265W |
| Electricity rate | 0.11USD/kWh |
| Retrofit capital cost | 36,000USD |
Results
| Actual LPD | 0.814W/ft² |
|---|---|
| LPD margin | 34.4% |
| Energy saved | 93,947kWh/yr |
| Payback | 3.5yr |
| Selected LPD allowance | 1.24W/ft² |
| Connected load | 19,536W |
| Connected power allowance | 29,760W |
| Allowance minus connected load | 10,224W |
| Equivalent controlled load | 17,582.4W |
| Legacy lighting energy | 188,892kWh/yr |
| Post-retrofit lighting energy | 94,944.96kWh/yr |
| Annual utility savings | 10,334.17USD/yr |
Connected LPD screen
- Connected power density · 0.81 / ≤ 1.24 W/ft² · Within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.