Interior parking garage retrofit

Estimate a 24-hour garage retrofit where lighting reduction controls affect annual energy but not connected watts in the screening comparison.

Space and installed power
ft²
W
Annual retrofit estimate
%
h/yr
W
USD/kWh
USD
Actual LPD
0.131W/ft²
LPD margin
12.5%
Energy saved
55,748.6kWh/yr
Payback
3.3yr

Installed power and allowance

Edit inputs ↓
Installed power and allowancePOWER DENSITYCONNECTED VS LIMITConnected0.131 W/ft²Controlled0.076 W/ft²Allowance0.15 W/ft²Energy saved annually55748.6 kWh/yr
Cobalt marks the selected LPD limit. The controlled load represents the annual energy model.

Connected LPD screen

Within screen
OutsideThresholdWithin
  • Connected power density0.13 / ≤ 0.15 W/ft² within screen

Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.

Additional readings
Selected LPD allowance0.15W/ft²
Connected load4,200W
Connected power allowance4,800W
Allowance minus connected load600W
Equivalent controlled load2,436W
Legacy lighting energy77,088kWh/yr
Post-retrofit lighting energy21,339.36kWh/yr
Annual utility savings7,247.32USD/yr

Worked calculation

US customary results for the original preset.

  1. Divide 4200 W of connected load by 32000 ft² to get 0.131 W/ft². The selected limit is 0.15 W/ft².
  2. After applying the control credit to annual use, compare 77088 kWh/yr before retrofit with 21339.4 kWh/yr after retrofit.
  3. At 0.13 USD/kWh, the annual cost difference is 7247.32 USD/yr. Simple payback is 3.31 yr.

Calculation method

Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.

Connected lighting power density
LPD = fixture count × input watts/floor area
Annual energy savings
ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
Simple payback
Years = retrofit cost/(ΔkWh × utility rate), when savings are positive

Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.

Sources and assumptions ↗