Open office LED retrofit
Compare the existing troffers with a lower-wattage LED replacement and a separate annual energy reduction from controls.
Inputs
View results ↑- Actual LPD
- 0.412W/ft²
- LPD margin
- 32.5%
- Energy saved
- 6,152.4kWh/yr
- Payback
- 3.8yr
Installed power and allowance
Edit inputs ↓Connected LPD screen
Within screen- Connected power density0.41 / ≤ 0.61 W/ft² within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Additional readings
| Selected LPD allowance | 0.61W/ft² |
|---|---|
| Connected load | 1,564W |
| Connected power allowance | 2,318W |
| Allowance minus connected load | 754W |
| Equivalent controlled load | 1,282.48W |
| Legacy lighting energy | 9,871.6kWh/yr |
| Post-retrofit lighting energy | 3,719.19kWh/yr |
| Annual utility savings | 1,107.43USD/yr |
Worked calculation
US customary results for the original preset.
- Divide 1564 W of connected load by 3800 ft² to get 0.412 W/ft². The selected limit is 0.61 W/ft².
- After applying the control credit to annual use, compare 9871.6 kWh/yr before retrofit with 3719.2 kWh/yr after retrofit.
- At 0.18 USD/kWh, the annual cost difference is 1107.43 USD/yr. Simple payback is 3.79 yr.
Calculation method
Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.
- Connected lighting power density
- LPD = fixture count × input watts/floor area
- Annual energy savings
- ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
- Simple payback
- Years = retrofit cost/(ΔkWh × utility rate), when savings are positive
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.
Sources and assumptions ↗Open office LED retrofit
Inputs
| Space type | Office · open plan |
|---|---|
| Lighted floor area | 3,800ft² |
| Fixture count | 46 |
| Installed watts per fixture | 34W |
| Control energy credit | 18% |
| Operating hours | 2,900h/yr |
| Legacy watts per fixture | 74W |
| Electricity rate | 0.18USD/kWh |
| Retrofit capital cost | 4,200USD |
Results
| Actual LPD | 0.412W/ft² |
|---|---|
| LPD margin | 32.5% |
| Energy saved | 6,152.4kWh/yr |
| Payback | 3.8yr |
| Selected LPD allowance | 0.61W/ft² |
| Connected load | 1,564W |
| Connected power allowance | 2,318W |
| Allowance minus connected load | 754W |
| Equivalent controlled load | 1,282.48W |
| Legacy lighting energy | 9,871.6kWh/yr |
| Post-retrofit lighting energy | 3,719.19kWh/yr |
| Annual utility savings | 1,107.43USD/yr |
Connected LPD screen
- Connected power density · 0.41 / ≤ 0.61 W/ft² · Within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.