Retail sales floor allowance
Compare the base sales floor allowance with connected track lighting before considering any additional display-light allowances.
Inputs
View results ↑- Actual LPD
- 1.135W/ft²
- LPD margin
- -8.1%
- Energy saved
- 3,232.3kWh/yr
- Payback
- 4.7yr
Installed power and allowance
Edit inputs ↓Connected LPD screen
Review needed- Connected power density1.13 / ≤ 1.05 W/ft² outside screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Additional readings
| Selected LPD allowance | 1.05W/ft² |
|---|---|
| Connected load | 2,496W |
| Connected power allowance | 2,310W |
| Allowance minus connected load | -186W |
| Equivalent controlled load | 2,371.2W |
| Legacy lighting energy | 12,480kWh/yr |
| Post-retrofit lighting energy | 9,247.68kWh/yr |
| Annual utility savings | 678.79USD/yr |
Worked calculation
US customary results for the original preset.
- Divide 2496 W of connected load by 2200 ft² to get 1.135 W/ft². The selected limit is 1.05 W/ft².
- After applying the control credit to annual use, compare 12480 kWh/yr before retrofit with 9247.7 kWh/yr after retrofit.
- At 0.21 USD/kWh, the annual cost difference is 678.79 USD/yr. Simple payback is 4.71 yr.
Calculation method
Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.
- Connected lighting power density
- LPD = fixture count × input watts/floor area
- Annual energy savings
- ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
- Simple payback
- Years = retrofit cost/(ΔkWh × utility rate), when savings are positive
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.
Sources and assumptions ↗Retail sales floor allowance
Inputs
| Space type | Retail · sales floor |
|---|---|
| Lighted floor area | 2,200ft² |
| Fixture count | 64 |
| Installed watts per fixture | 39W |
| Control energy credit | 5% |
| Operating hours | 3,900h/yr |
| Legacy watts per fixture | 50W |
| Electricity rate | 0.21USD/kWh |
| Retrofit capital cost | 3,200USD |
Results
| Actual LPD | 1.135W/ft² |
|---|---|
| LPD margin | -8.1% |
| Energy saved | 3,232.3kWh/yr |
| Payback | 4.7yr |
| Selected LPD allowance | 1.05W/ft² |
| Connected load | 2,496W |
| Connected power allowance | 2,310W |
| Allowance minus connected load | -186W |
| Equivalent controlled load | 2,371.2W |
| Legacy lighting energy | 12,480kWh/yr |
| Post-retrofit lighting energy | 9,247.68kWh/yr |
| Annual utility savings | 678.79USD/yr |
Connected LPD screen
- Connected power density · 1.13 / ≤ 1.05 W/ft² · Outside screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.