Lighting Power Density

Compare connected LPD to an ASHRAE allowance and estimate LED retrofit energy, cost savings, and simple payback.

Space and installed power
ft²
W
Annual retrofit estimate
%
h/yr
W
USD/kWh
USD
Actual LPD
0.507W/ft²
LPD margin
16.9%
Energy saved
4,126.7kWh/yr
Payback
4.4yr

Installed power and allowance

Edit inputs ↓
Installed power and allowancePOWER DENSITYCONNECTED VS LIMITConnected0.507 W/ft²Controlled0.405 W/ft²Allowance0.61 W/ft²Energy saved annually4126.7 kWh/yr
Cobalt marks the selected LPD limit. The controlled load represents the annual energy model.

Connected LPD screen

Within screen
OutsideThresholdWithin
  • Connected power density0.51 / ≤ 0.61 W/ft² within screen

Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.

Additional readings
Selected LPD allowance0.61W/ft²
Connected load1,216W
Connected power allowance1,464W
Allowance minus connected load248W
Equivalent controlled load972.8W
Legacy lighting energy7,142.4kWh/yr
Post-retrofit lighting energy3,015.68kWh/yr
Annual utility savings660.28USD/yr

Calculation method

Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.

Connected lighting power density
LPD = fixture count × input watts/floor area
Annual energy savings
ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
Simple payback
Years = retrofit cost/(ΔkWh × utility rate), when savings are positive

Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.

Sources and assumptions ↗