Lighting Power Density
Compare connected LPD to an ASHRAE allowance and estimate LED retrofit energy, cost savings, and simple payback.
Inputs
View results ↑- Actual LPD
- 0.507W/ft²
- LPD margin
- 16.9%
- Energy saved
- 4,126.7kWh/yr
- Payback
- 4.4yr
Installed power and allowance
Edit inputs ↓Connected LPD screen
Within screenOutsideThresholdWithin
- Connected power density0.51 / ≤ 0.61 W/ft² within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Additional readings
| Selected LPD allowance | 0.61W/ft² |
|---|---|
| Connected load | 1,216W |
| Connected power allowance | 1,464W |
| Allowance minus connected load | 248W |
| Equivalent controlled load | 972.8W |
| Legacy lighting energy | 7,142.4kWh/yr |
| Post-retrofit lighting energy | 3,015.68kWh/yr |
| Annual utility savings | 660.28USD/yr |
Calculation method
Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.
- Connected lighting power density
- LPD = fixture count × input watts/floor area
- Annual energy savings
- ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
- Simple payback
- Years = retrofit cost/(ΔkWh × utility rate), when savings are positive
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.
Sources and assumptions ↗LightingLuxLab · US customary
Lighting Power Density
Inputs
| Space type | Office · open plan |
|---|---|
| Lighted floor area | 2,400ft² |
| Fixture count | 32 |
| Installed watts per fixture | 38W |
| Control energy credit | 20% |
| Operating hours | 3,100h/yr |
| Legacy watts per fixture | 72W |
| Electricity rate | 0.16USD/kWh |
| Retrofit capital cost | 2,900USD |
Results
| Actual LPD | 0.507W/ft² |
|---|---|
| LPD margin | 16.9% |
| Energy saved | 4,126.7kWh/yr |
| Payback | 4.4yr |
| Selected LPD allowance | 0.61W/ft² |
| Connected load | 1,216W |
| Connected power allowance | 1,464W |
| Allowance minus connected load | 248W |
| Equivalent controlled load | 972.8W |
| Legacy lighting energy | 7,142.4kWh/yr |
| Post-retrofit lighting energy | 3,015.68kWh/yr |
| Annual utility savings | 660.28USD/yr |
Connected LPD screen
- Connected power density · 0.51 / ≤ 0.61 W/ft² · Within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.