Interior parking garage retrofit
Estimate a 24-hour garage retrofit where lighting reduction controls affect annual energy but not connected watts in the screening comparison.
Inputs
View results ↑- Actual LPD
- 0.131W/ft²
- LPD margin
- 12.5%
- Energy saved
- 55,748.6kWh/yr
- Payback
- 3.3yr
Installed power and allowance
Edit inputs ↓Connected LPD screen
Within screen- Connected power density0.13 / ≤ 0.15 W/ft² within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Additional readings
| Selected LPD allowance | 0.15W/ft² |
|---|---|
| Connected load | 4,200W |
| Connected power allowance | 4,800W |
| Allowance minus connected load | 600W |
| Equivalent controlled load | 2,436W |
| Legacy lighting energy | 77,088kWh/yr |
| Post-retrofit lighting energy | 21,339.36kWh/yr |
| Annual utility savings | 7,247.32USD/yr |
Worked calculation
US customary results for the original preset.
- Divide 4200 W of connected load by 32000 ft² to get 0.131 W/ft². The selected limit is 0.15 W/ft².
- After applying the control credit to annual use, compare 77088 kWh/yr before retrofit with 21339.4 kWh/yr after retrofit.
- At 0.13 USD/kWh, the annual cost difference is 7247.32 USD/yr. Simple payback is 3.31 yr.
Calculation method
Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.
- Connected lighting power density
- LPD = fixture count × input watts/floor area
- Annual energy savings
- ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
- Simple payback
- Years = retrofit cost/(ΔkWh × utility rate), when savings are positive
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.
Sources and assumptions ↗Interior parking garage retrofit
Inputs
| Space type | Parking garage · interior |
|---|---|
| Lighted floor area | 32,000ft² |
| Fixture count | 100 |
| Installed watts per fixture | 42W |
| Control energy credit | 42% |
| Operating hours | 8,760h/yr |
| Legacy watts per fixture | 88W |
| Electricity rate | 0.13USD/kWh |
| Retrofit capital cost | 24,000USD |
Results
| Actual LPD | 0.131W/ft² |
|---|---|
| LPD margin | 12.5% |
| Energy saved | 55,748.6kWh/yr |
| Payback | 3.3yr |
| Selected LPD allowance | 0.15W/ft² |
| Connected load | 4,200W |
| Connected power allowance | 4,800W |
| Allowance minus connected load | 600W |
| Equivalent controlled load | 2,436W |
| Legacy lighting energy | 77,088kWh/yr |
| Post-retrofit lighting energy | 21,339.36kWh/yr |
| Annual utility savings | 7,247.32USD/yr |
Connected LPD screen
- Connected power density · 0.13 / ≤ 0.15 W/ft² · Within screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.