Retail sales floor allowance

Compare the base sales floor allowance with connected track lighting before considering any additional display-light allowances.

Space and installed power
ft²
W
Annual retrofit estimate
%
h/yr
W
USD/kWh
USD
Actual LPD
1.135W/ft²
LPD margin
-8.1%
Energy saved
3,232.3kWh/yr
Payback
4.7yr

Installed power and allowance

Edit inputs ↓
Installed power and allowancePOWER DENSITYCONNECTED VS LIMITConnected1.135 W/ft²Controlled1.078 W/ft²Allowance1.05 W/ft²Energy saved annually3232.3 kWh/yr
Cobalt marks the selected LPD limit. The controlled load represents the annual energy model.

Connected LPD screen

Review needed
OutsideThresholdWithin
  • Connected power density1.13 / ≤ 1.05 W/ft² outside screen

Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.

Additional readings
Selected LPD allowance1.05W/ft²
Connected load2,496W
Connected power allowance2,310W
Allowance minus connected load-186W
Equivalent controlled load2,371.2W
Legacy lighting energy12,480kWh/yr
Post-retrofit lighting energy9,247.68kWh/yr
Annual utility savings678.79USD/yr

Worked calculation

US customary results for the original preset.

  1. Divide 2496 W of connected load by 2200 ft² to get 1.135 W/ft². The selected limit is 1.05 W/ft².
  2. After applying the control credit to annual use, compare 12480 kWh/yr before retrofit with 9247.7 kWh/yr after retrofit.
  3. At 0.21 USD/kWh, the annual cost difference is 678.79 USD/yr. Simple payback is 4.71 yr.

Calculation method

Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.

Connected lighting power density
LPD = fixture count × input watts/floor area
Annual energy savings
ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
Simple payback
Years = retrofit cost/(ΔkWh × utility rate), when savings are positive

Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.

Sources and assumptions ↗