ASME B31.3 flexibility screen

Carbon steel U-loop on a hot process run

A carbon steel pipe rack needs space for a symmetric loop between two anchors after startup.

Inputs

Thermal duty
Flexibility screen
Movement ΔL
3.84in
Minimum leg
16.16ft
Leg stress
16.12ksi
Stress margin
3.88ksi
Leg within entered Sₐ

The provided leg meets the entered stress range in the guided-cantilever screen.

Thermal movement and routing

Thermal movement and routingArrows indicate the direction of thermal movement. The routed legs and dimensions represent the selected layout.RUN ΔL3.84 inLOOP WIDTH12.6 ftWHFLEXING PIPEMIN. LEG16.16 ftPROVIDED LEG18 ftSTRESS MARGIN3.88 ksi
Arrows indicate the direction of thermal movement. The routed legs and dimensions represent the selected layout.

All calculated values
Temperature change ΔT320 °F
Signed run movement ΔL3.84 in
Motion assigned to each leg1.92 in
Minimum flexing leg16.158 ft
Width at minimum U-loop height11.31 ft
Width at provided U-loop height12.6 ft
Screened displacement stress16.12 ksi
Available stress range3.88 ksi
Allowable range used80.6 %
Nominal elastic modulus29.01 Mpsi
Linear expansion coefficient0.000012 1/°C

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Calculate signed pipe movement3.84 in
  2. Find the flexing leg length16.158 ft
  3. Compare with available stress range3.88 ksi

The screen splits movement across two legs. Check both leg length and proposed loop width against the rack envelope.

Model and limits

Use the length between effective anchors and the install-to-operating temperature difference. The guided-cantilever screen assigns the full displacement to a single L-leg or shares it equally across the two idealized legs of a Z-offset or U-loop.

Use a project-approved allowable displacement stress range Sₐ. Representative moduli and coefficients are constant over the entered temperature range. Confirm temperature-dependent properties, anchor loads, direction of movement, elbow flexibility, fatigue cycles and stress intensification using the governing B31.3 edition and a pipe stress analysis. U-loop width is a layout estimate from the entered aspect ratio.

View equations and references