IEC 60534-2-1 / ISA-75.01
Cooling water valve at 180 GPM
A cooling water branch needs 180 GPM with 28 psi available across its control valve.
Inputs
Results
Edit inputs- Required Cv
- 33.98
- Required Kv
- 29.39
- Choke ΔP
- 96.8psi
- Cavitation σ
- 4.27
The estimated throat pressure and cavitation index are above their onset thresholds.
Valve pressure recovery
All calculated values
| Required Cv | 33.98 |
|---|---|
| Required Kv | 29.39 |
| Capacity regime | Unchoked |
| Actual pressure drop | 28 psi |
| Choke pressure drop | 96.84 psi |
| Choke recovery basis | Bare-valve Fₗ |
| Effective sizing drop | 28 psi |
| Liquid critical pressure factor Fꜰ | 0.9566 |
| Estimated vena contracta pressure | 85.43 psia |
| Cavitation index σ | 4.269 |
| Actual / choke drop | 28.9 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Find the available drop28 psi
- Limit the drop at choking28 psi
- Size the required Cv33.98
The available differential governs Cv because this duty stays below the choke drop. Compare the required Cv with the OEM curve at the intended travel.
Model and limits
Use absolute inlet, outlet, vapor and critical pressures for the single-phase turbulent liquid sizing basis. Specific gravity is relative to water. Use vapor pressure at the actual flowing temperature.
Enter matching OEM Fₗₚ and Fₚ for attached fittings. A zero Fₗₚ leaves a bare-valve choke estimate. The pressure profile divides the effective drop by the square of the recovery factor to estimate throat pressure. A low σ or throat pressure indicates cavitation risk. P₂ below Pᵥ indicates flashing. Trim-specific σᵢ, viscous correction, damage limits and multiphase flow require separate review.
View equations and references