IEC 60534-2-1 / ISA-75.01
Outlet exactly at vapor pressure
A hot liquid discharges at the measured vapor pressure for the process temperature.
Inputs
Results
Edit inputs- Required Cv
- 11.66
- Required Kv
- 10.09
- Choke ΔP
- 61.1psi
- Cavitation σ
- 1
Outlet pressure equals vapor pressure. Small operating changes can shift the outlet to flashing. Choked flow caps the sizing drop.
Valve pressure recovery
All calculated values
| Required Cv | 11.66 |
|---|---|
| Required Kv | 10.09 |
| Capacity regime | Choked |
| Actual pressure drop | 77 psi |
| Choke pressure drop | 61.06 psi |
| Choke recovery basis | Bare-valve Fₗ |
| Effective sizing drop | 61.06 psi |
| Liquid critical pressure factor Fꜰ | 0.9338 |
| Estimated vena contracta pressure | 26.15 psia |
| Cavitation index σ | 1 |
| Actual / choke drop | 126.1 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Find the available drop77 psi
- Limit the drop at choking61.06 psi
- Size the required Cv11.66
This is the saturation boundary. A small decrease in outlet pressure or increase in temperature can produce sustained flashing.
Model and limits
Use absolute inlet, outlet, vapor and critical pressures for the single-phase turbulent liquid sizing basis. Specific gravity is relative to water. Use vapor pressure at the actual flowing temperature.
Enter matching OEM Fₗₚ and Fₚ for attached fittings. A zero Fₗₚ leaves a bare-valve choke estimate. The pressure profile divides the effective drop by the square of the recovery factor to estimate throat pressure. A low σ or throat pressure indicates cavitation risk. P₂ below Pᵥ indicates flashing. Trim-specific σᵢ, viscous correction, damage limits and multiphase flow require separate review.
View equations and references