IEC 60534-2-1 / ISA-75.01

Hot condensate flashing at the outlet

A hot condensate valve discharges to a line where absolute pressure is below the liquid vapor pressure.

Inputs

Liquid duty
Trim factors
Use the OEM value with attached fittings. Enter 0 for the bare-valve screen.
Use the OEM value for the selected trim and opening.
Required Cv
7.45
Required Kv
6.44
Choke ΔP
47.8psi
Cavitation σ
0.82
Flashing indicated

Outlet pressure remains below vapor pressure, so vapor can persist beyond the valve. Choked flow caps the sizing drop.

Valve pressure recovery

Valve pressure recoveryThe pressure profile follows the inlet, vena contracta and outlet. The dashed line is liquid vapor pressure.INLET P₁130 psiaTHROAT Pᵥ꜀55.3 psiaOUTLET P₂45 psiaVAPOR Pᵥ60 psiaACTUAL ΔP85 psiCHOKE ΔP47.8 psi
The pressure profile follows the inlet, vena contracta and outlet. The dashed line is liquid vapor pressure.

All calculated values
Required Cv7.45
Required Kv6.44
Capacity regimeChoked
Actual pressure drop85 psi
Choke pressure drop47.81 psi
Choke recovery basisBare-valve Fₗ
Effective sizing drop47.81 psi
Liquid critical pressure factor Fꜰ0.9217
Estimated vena contracta pressure55.3 psia
Cavitation index σ0.824
Actual / choke drop177.8 %

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Find the available drop85 psi
  2. Limit the drop at choking47.81 psi
  3. Size the required Cv7.45

Vapor can persist at the outlet. The choked sizing differential limits capacity even as outlet pressure drops farther.

Model and limits

Use absolute inlet, outlet, vapor and critical pressures for the single-phase turbulent liquid sizing basis. Specific gravity is relative to water. Use vapor pressure at the actual flowing temperature.

Enter matching OEM Fₗₚ and Fₚ for attached fittings. A zero Fₗₚ leaves a bare-valve choke estimate. The pressure profile divides the effective drop by the square of the recovery factor to estimate throat pressure. A low σ or throat pressure indicates cavitation risk. P₂ below Pᵥ indicates flashing. Trim-specific σᵢ, viscous correction, damage limits and multiphase flow require separate review.