ASME B31.3 flexibility screen
CPVC process-water expansion loop
A CPVC process-water line sees a 40 °C temperature increase after commissioning.
Inputs
Results
Edit inputs- Movement ΔL
- 78.08mm
- Minimum leg
- 2.89m
- Leg stress
- 3.48MPa
- Stress margin
- 0.52MPa
The provided leg meets the entered stress range in the guided-cantilever screen. Confirm CPVC temperature and long-term modulus with the manufacturer.
Thermal movement and routing
All calculated values
| Temperature change ΔT | 40 °C |
|---|---|
| Signed run movement ΔL | 78.08 mm |
| Motion assigned to each leg | 39.04 mm |
| Minimum flexing leg | 2.893 m |
| Width at minimum U-loop height | 2.314 m |
| Width at provided U-loop height | 2.48 m |
| Screened displacement stress | 3.48 MPa |
| Available stress range | 0.52 MPa |
| Allowable range used | 87.1 % |
| Nominal elastic modulus | 2.5 GPa |
| Linear expansion coefficient | 0.000061 1/°C |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Calculate signed pipe movement78.08 mm
- Find the flexing leg length2.893 m
- Compare with available stress range0.52 MPa
CPVC grows more per degree than steel. Verify the permissible temperature, long-term modulus and anchor loads with the manufacturer.
Model and limits
Use the length between effective anchors and the install-to-operating temperature difference. The guided-cantilever screen assigns the full displacement to a single L-leg or shares it equally across the two idealized legs of a Z-offset or U-loop.
Use a project-approved allowable displacement stress range Sₐ. Representative moduli and coefficients are constant over the entered temperature range. Confirm temperature-dependent properties, anchor loads, direction of movement, elbow flexibility, fatigue cycles and stress intensification using the governing B31.3 edition and a pipe stress analysis. U-loop width is a layout estimate from the entered aspect ratio.
View equations and references