Installed flow characteristic
Equal-percentage trim at low authority
A long distribution circuit takes most of the available pressure when the valve is open.
Inputs
Results
Edit inputs- Authority a
- 0.125
- Inherent flow
- 33.4%
- Installed flow
- 70.8%
- Flow shift
- 37.4pp
The installed curve can rise much faster than the inherent trim curve. Review controllability over the duty range.
Inherent vs installed flow
All calculated values
| Full-open valve authority | 0.125 |
|---|---|
| Inherent flow fraction | 33.44 % |
| Installed flow fraction | 70.84 % |
| Installed minus inherent | 37.4 pp |
| Total available pressure | 40 psi |
| Valve share at selected lift | 56.1 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Allocate full-open pressure0.125
- Read the selected trim33.44 %
- Apply system resistance70.84 %
The installed curve rises above the inherent Cv curve. Compare the process gain near the actual operating travel.
Model and limits
Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.
Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.
View equations and references