Installed flow characteristic

Fully open valve normalization

An engineer checks the reference condition for a plant flow-control loop at full travel.

Inputs

Full-open duty
Valve characteristic
Authority a
0.25
Inherent flow
100%
Installed flow
100%
Flow shift
0pp
Authority curve available

Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.

Inherent vs installed flow

Inherent vs installed flowEach curve is normalized to fully open flow. Markers show the selected stem lift.0%50%100%0%STEM LIFT100%INHERENTINSTALLEDAUTHORITY0.25STEM LIFT100 %FLOW SHIFT0 pp
Each curve is normalized to fully open flow. Markers show the selected stem lift.

All calculated values
Full-open valve authority0.25
Inherent flow fraction100 %
Installed flow fraction100 %
Installed minus inherent0 pp
Total available pressure36 psi
Valve share at selected lift25 %

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Allocate full-open pressure0.25
  2. Read the selected trim100 %
  3. Apply system resistance100 %

Both curves reach 100% full-open flow. At that point the valve share of pressure equals the full-open authority.

Model and limits

Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.

Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.

View equations and references

Worked examples