Installed flow characteristic
Trim in a negligible-loss test rig
The test rig holds pressure across the valve effectively constant, with negligible external friction.
Inputs
Results
Edit inputs- Authority a
- 1
- Inherent flow
- 13.1%
- Installed flow
- 13.1%
- Flow shift
- 0pp
Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.
Inherent vs installed flow
All calculated values
| Full-open valve authority | 1 |
|---|---|
| Inherent flow fraction | 13.08 % |
| Installed flow fraction | 13.08 % |
| Installed minus inherent | 0 pp |
| Total available pressure | 120 kPa |
| Valve share at selected lift | 100 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Allocate full-open pressure1
- Read the selected trim13.08 %
- Apply system resistance13.08 %
Authority approaches unity and the curves coincide, a useful limit for checking installed-flow normalization.
Model and limits
Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.
Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.
View equations and references