Installed flow characteristic
30:1 equal-percentage rangeability
The trim vendor offers 30:1 and 50:1 inherent rangeability for a pressure-control valve.
Inputs
Results
Edit inputs- Authority a
- 0.429
- Inherent flow
- 21.6%
- Installed flow
- 32.1%
- Flow shift
- 10.4pp
Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.
Inherent vs installed flow
All calculated values
| Full-open valve authority | 0.4286 |
|---|---|
| Inherent flow fraction | 21.64 % |
| Installed flow fraction | 32.07 % |
| Installed minus inherent | 10.43 pp |
| Total available pressure | 35 psi |
| Valve share at selected lift | 94.1 % |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Allocate full-open pressure0.4286
- Read the selected trim21.64 %
- Apply system resistance32.07 %
Switch rangeability with the pressure allocation fixed to see how the shape changes at the same stem position.
Model and limits
Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.
Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.
View equations and references