Installed flow characteristic

30:1 equal-percentage rangeability

The trim vendor offers 30:1 and 50:1 inherent rangeability for a pressure-control valve.

Inputs

Full-open duty
Valve characteristic
Authority a
0.429
Inherent flow
21.6%
Installed flow
32.1%
Flow shift
10.4pp
Authority curve available

Compare inherent and installed flow at the selected travel. The screen uses a fixed available pressure and a square-law system.

Inherent vs installed flow

Inherent vs installed flowEach curve is normalized to fully open flow. Markers show the selected stem lift.0%50%100%0%STEM LIFT100%INHERENTINSTALLEDAUTHORITY0.429STEM LIFT55 %FLOW SHIFT10.4 pp
Each curve is normalized to fully open flow. Markers show the selected stem lift.

All calculated values
Full-open valve authority0.4286
Inherent flow fraction21.64 %
Installed flow fraction32.07 %
Installed minus inherent10.43 pp
Total available pressure35 psi
Valve share at selected lift94.1 %

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Allocate full-open pressure0.4286
  2. Read the selected trim21.64 %
  3. Apply system resistance32.07 %

Switch rangeability with the pressure allocation fixed to see how the shape changes at the same stem position.

Model and limits

Full-open valve authority is the fraction of the available differential consumed by the fully open valve. The installed curve assumes fixed available differential and square-law friction outside the valve.

Travel h and flow fractions run from 0 to 1. At shutoff all trims are set to zero. Equal-percentage rangeability applies over the throttling range just above shutoff. Quick opening uses an illustrative square-root curve. Authority below 0.25 prompts a loop review. Use actual OEM Cv versus travel and system characteristics for control tuning.

View equations and references