ISO 5167-2 / ASME MFC-3M

Four-inch cooling water orifice

A four-inch process-water line uses a 2.4-inch bore and a measured differential of 3.5 psi.

Inputs

Orifice geometry
Flow and fluid
Annual energy
Beta ratio
0.596
Volume flow
209.9GPM
Meter ΔP
3.5psi
Permanent ΔP
2.2psi
Within basic meter screen

β, bore, pipe ID and Re meet the displayed screening bounds. Confirm tapping geometry, the calibrated coefficient and gas expansibility.

Orifice and vena contracta

Orifice and vena contractaThe jet contracts after the plate and then recovers. The permanent loss remains after pressure recovery.PIPE ID D4.03 inBORE d2.4 inBETA β0.596FLOWPLATEVENA CONTRACTAMETER ΔP3.5 psiPERMANENT2.2 psiHEAD LOSS5.06 ft
The jet contracts after the plate and then recovers. The permanent loss remains after pressure recovery.

All calculated values
Diameter ratio β0.5961
Upstream volume flow209.95 GPM
Mass flow104,914.41 lb/h
Meter differential ΔP3.5 psi
Combined flow multiplier E1.0698
Pipe Reynolds number164,589
Unrecovered pressure loss2.19 psi
Unrecovered head5.062 ft
Unrecovered share62.6 %
Input power for loss0.286 kW
Annual energy for loss2,057.3 kWh/yr
Annual energy cost308.6 $/yr

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Find the diameter ratio0.5961
  2. Solve the meter equation209.95 GPM
  3. Keep the unrecovered loss2.19 psi

The meter signal includes pressure that recovers downstream. Use only the unrecovered portion for annual power cost.

Model and limits

The screen uses a concentric sharp-edged plate in a full pipe, inlet density, an entered discharge coefficient and expansibility. The default Cd of 0.61 is a screening estimate. Enter a calibrated value or calculate Cd for your tapping geometry. For a liquid, set expansibility to 1. The velocity-of-approach factor is included in E.

The screen uses β from 0.20 to 0.75, pipe ID from 50 to 1,000 mm and bore of at least 12.5 mm. It uses the largest Reynolds floor for corner, D and D/2, and flange tappings. Confirm the actual tapping limits, straight runs, roughness, Cd and gas expansibility. The permanent-loss multiplier is an approximation. Gas volume is at inlet conditions and the energy estimate is a hydraulic power proxy.

View equations and references

Worked examples