1:150 ventilation for a 1,500 ft² attic

A vented attic has 1,500 ft² of floor area. Compare the baseline 1:150 target with the existing soffit and ridge ratings.

Worked calculation

Divide the attic area by 150 for 10 ft² of total net free area, then convert to 1,440 in². Each side contributes 720 in² in this balanced example.

Change the inputs to test your own measurements. Reset restores this example.

Inputs

Units
Ventilation target
ft²
Low intake
in²
High exhaust
ft
in²/ft

Results

Live

Low intake and high exhaust balanceRequired total NFA 1,440 in². Target per vent group 720 in². RIDGEIntakeExhaust720 in²720 in²
Low intake and high exhaust balance Schematic
Installed low intake
720 in²
Installed high exhaust
720 in²
Installed total NFA
1,440 in²
Balanced NFA equivalent
1,440 in²
Upper share of installed NFA
50%
Intake shortfall
0 in²
Exhaust shortfall
0 in²
Total soffit vent units needed
12
Total active ridge vent needed
40 ft
Additional soffit units
0
Additional active ridge vent
0 ft

Apply this example to your roof

Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.

Read the calculator method and references

Frequently asked questions

What is the 1:150 target in square inches for 1,500 ft²?

It is 1,440 in² of total NFA, split into two 720 in² planning targets.

Should the attic floor area include the covered porch?

Use the floor area of the connected vented attic. Treat an isolated porch cavity according to its own assembly.