1:150 ventilation for a 1,500 ft² attic
A vented attic has 1,500 ft² of floor area. Compare the baseline 1:150 target with the existing soffit and ridge ratings.
Worked calculation
Divide the attic area by 150 for 10 ft² of total net free area, then convert to 1,440 in². Each side contributes 720 in² in this balanced example.
Change the inputs to test your own measurements. Reset restores this example.
Results
LiveCorrect the highlighted inputs to update your results.
- Required total NFA
- Target per vent group
- Installed low intake
- Installed high exhaust
- Installed total NFA
- Balanced NFA equivalent
- Upper share of installed NFA
- Intake shortfall
- Exhaust shortfall
- Total soffit vent units needed
- Total active ridge vent needed
- Additional soffit units
- Additional active ridge vent
Worksheet inputs US customary
- Vented attic floor area
- 1,500 ft²
- Ventilation ratio
- 1:150 · baseline
- Soffit vent units
- 12
- Net free area per soffit vent
- 60 in²
- Exhaust system
- Continuous ridge vent
- Active ridge vent length
- 40 ft
- Ridge vent NFA per length
- 18 in²/ft
Apply this example to your roof
Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.
Frequently asked questions
What is the 1:150 target in square inches for 1,500 ft²?
It is 1,440 in² of total NFA, split into two 720 in² planning targets.
Should the attic floor area include the covered porch?
Use the floor area of the connected vented attic. Treat an isolated porch cavity according to its own assembly.