Ventilation check with only 20 ft of ridge

A 1,600 ft² attic has a short active ridge and 18 in² of documented ridge NFA per foot.

Worked calculation

The ridge delivers 360 in² and the high-side target is 768 in². The resulting 408 in² gap is the equivalent of about 22.67 additional feet at the same rating.

Change the inputs to test your own measurements. Reset restores this example.

Inputs

Units
Ventilation target
ft²
Low intake
in²
High exhaust
ft
in²/ft

Results

Live

Low intake and high exhaust balanceRequired total NFA 1,536 in². Target per vent group 768 in². RIDGEIntakeExhaust840 in²360 in²
Low intake and high exhaust balance Schematic
Installed low intake
840 in²
Installed high exhaust
360 in²
Installed total NFA
1,200 in²
Balanced NFA equivalent
720 in²
Upper share of installed NFA
30%
Intake shortfall
0 in²
Exhaust shortfall
408 in²
Total soffit vent units needed
14
Total active ridge vent needed
42.67 ft
Additional soffit units
0
Additional active ridge vent
22.67 ft
  • One or both vent groups are below the 50/50 planning target.

Apply this example to your roof

Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.

Read the calculator method and references

Frequently asked questions

Is a 20-foot ridge enough for this 1,600 ft² attic?

At the entered rating and ratio, it covers 360 of the 768 in² high-side target. Review another suitable high exhaust layout.

Why can active ridge vent length be shorter than the ridge cap?

End setbacks, blocked slots and unvented sections reduce the continuous opening that contributes NFA.