Static box vent retrofit for a 1,000 ft² attic

A retrofit has seven static box vents rated at 50 in² each. Estimate how many more would meet the high-side planning target.

Worked calculation

The 1:150 target is 480 in² high. Seven boxes supply 350 in², leaving 130 in². Three more 50 in² boxes cover that gap.

Change the inputs to test your own measurements. Reset restores this example.

Inputs

Units
Ventilation target
ft²
Low intake
in²
High exhaust
in²

Results

Live

Low intake and high exhaust balanceRequired total NFA 960 in². Target per vent group 480 in². BOX VENTSIntakeExhaust500 in²350 in²
Low intake and high exhaust balance Schematic
Installed low intake
500 in²
Installed high exhaust
350 in²
Installed total NFA
850 in²
Balanced NFA equivalent
700 in²
Upper share of installed NFA
41.18%
Intake shortfall
0 in²
Exhaust shortfall
130 in²
Total soffit vent units needed
10
Total high exhaust units needed
10
Additional soffit units
0
Additional high exhaust units
3
  • One or both vent groups are below the 50/50 planning target.

Apply this example to your roof

Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.

Read the calculator method and references

Frequently asked questions

How many static box vents would fill the 130 in² shortfall?

Three boxes rated at 50 in² apiece. Recheck location and the resulting intake balance once the layout is set.

Why use a static vent rating instead of its outside dimensions?

Net free area accounts for louvers, screens and components that restrict the clear opening.