Static box vent retrofit for a 1,000 ft² attic
A retrofit has seven static box vents rated at 50 in² each. Estimate how many more would meet the high-side planning target.
Worked calculation
The 1:150 target is 480 in² high. Seven boxes supply 350 in², leaving 130 in². Three more 50 in² boxes cover that gap.
Change the inputs to test your own measurements. Reset restores this example.
Results
LiveCorrect the highlighted inputs to update your results.
- Required total NFA
- Target per vent group
- Installed low intake
- Installed high exhaust
- Installed total NFA
- Balanced NFA equivalent
- Upper share of installed NFA
- Intake shortfall
- Exhaust shortfall
- Total soffit vent units needed
- Total high exhaust units needed
- Additional soffit units
- Additional high exhaust units
- One or both vent groups are below the 50/50 planning target.
Worksheet inputs US customary
- Vented attic floor area
- 1,000 ft²
- Ventilation ratio
- 1:150 · baseline
- Soffit vent units
- 10
- Net free area per soffit vent
- 50 in²
- Exhaust system
- Static box vents
- Exhaust vents installed or planned
- 7
- Net free area per exhaust vent
- 50 in²
Apply this example to your roof
Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.
Frequently asked questions
How many static box vents would fill the 130 in² shortfall?
Three boxes rated at 50 in² apiece. Recheck location and the resulting intake balance once the layout is set.
Why use a static vent rating instead of its outside dimensions?
Net free area accounts for louvers, screens and components that restrict the clear opening.