Check attic ventilation with blocked soffits
A 1,200 ft² attic has an existing ridge vent, but insulation blocks all low vents. Estimate the planning intake needed after clearing the path.
Worked calculation
With low intake at zero, the balanced equivalent is zero. At 1:150 the low target is 576 in², which corresponds to 12 unblocked 48 in² soffit vents.
Change the inputs to test your own measurements. Reset restores this example.
Results
LiveCorrect the highlighted inputs to update your results.
- Required total NFA
- Target per vent group
- Installed low intake
- Installed high exhaust
- Installed total NFA
- Balanced NFA equivalent
- Upper share of installed NFA
- Intake shortfall
- Exhaust shortfall
- Total soffit vent units needed
- Total active ridge vent needed
- Additional soffit units
- Additional active ridge vent
- High exhaust exceeds the low intake NFA. Add or clear low intake before relying on the exhaust rating.
- One or both vent groups are below the 50/50 planning target.
Worksheet inputs US customary
- Vented attic floor area
- 1,200 ft²
- Ventilation ratio
- 1:150 · baseline
- Soffit vent units
- 0
- Net free area per soffit vent
- 48 in²
- Exhaust system
- Continuous ridge vent
- Active ridge vent length
- 32 ft
- Ridge vent NFA per length
- 18 in²/ft
Apply this example to your roof
Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.
Frequently asked questions
Why does the blocked-soffit case show zero balanced equivalent?
The model pairs the smaller intake or exhaust capacity with an equal amount on the other side. Here the intake is zero.
What measurement changes after installing soffit baffles?
Count the vents actually connected to an open air path, then enter their documented NFA per unit.