Check attic ventilation with blocked soffits

A 1,200 ft² attic has an existing ridge vent, but insulation blocks all low vents. Estimate the planning intake needed after clearing the path.

Worked calculation

With low intake at zero, the balanced equivalent is zero. At 1:150 the low target is 576 in², which corresponds to 12 unblocked 48 in² soffit vents.

Change the inputs to test your own measurements. Reset restores this example.

Inputs

Units
Ventilation target
ft²
Low intake
in²
High exhaust
ft
in²/ft

Results

Live

Low intake and high exhaust balanceRequired total NFA 1,152 in². Target per vent group 576 in². RIDGEIntakeExhaust0 in²576 in²
Low intake and high exhaust balance Schematic
Installed low intake
0 in²
Installed high exhaust
576 in²
Installed total NFA
576 in²
Balanced NFA equivalent
0 in²
Upper share of installed NFA
100%
Intake shortfall
576 in²
Exhaust shortfall
0 in²
Total soffit vent units needed
12
Total active ridge vent needed
32 ft
Additional soffit units
12
Additional active ridge vent
0 ft
  • High exhaust exceeds the low intake NFA. Add or clear low intake before relying on the exhaust rating.
  • One or both vent groups are below the 50/50 planning target.

Apply this example to your roof

Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.

Read the calculator method and references

Frequently asked questions

Why does the blocked-soffit case show zero balanced equivalent?

The model pairs the smaller intake or exhaust capacity with an equal amount on the other side. Here the intake is zero.

What measurement changes after installing soffit baffles?

Count the vents actually connected to an open air path, then enter their documented NFA per unit.