1:300 planning case for a 1,800 ft² attic

An attic design is being evaluated for the reduced 1:300 ratio. Test a 24 ft active ridge with 12 soffit vents.

Worked calculation

The total target is 864 in². This layout has 432 in² at the ridge and 504 in² low. The installed upper share is about 46.15%.

Change the inputs to test your own measurements. Reset restores this example.

Inputs

Units
Ventilation target
ft²
Low intake
in²
High exhaust
ft
in²/ft

Results

Live

Low intake and high exhaust balanceRequired total NFA 864 in². Target per vent group 432 in². RIDGEIntakeExhaust504 in²432 in²
Low intake and high exhaust balance Schematic
Installed low intake
504 in²
Installed high exhaust
432 in²
Installed total NFA
936 in²
Balanced NFA equivalent
864 in²
Upper share of installed NFA
46.15%
Intake shortfall
0 in²
Exhaust shortfall
0 in²
Total soffit vent units needed
11
Total active ridge vent needed
24 ft
Additional soffit units
0
Additional active ridge vent
0 ft
  • Verify eligibility for 1:300 under the adopted code, including upper-vent distribution and applicable vapor-retarder conditions.

Apply this example to your roof

Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.

Read the calculator method and references

Frequently asked questions

What upper vent share does the 24-foot ridge give here?

Its 432 in² of NFA is about 46.15% of the installed 936 in² total.

Does the 46% upper share alone establish 1:300 eligibility?

Check the applicable adopted code, placement distances and climate-zone vapor-retarder conditions as well.