Turbine exhaust with undersized soffit intake
An attic has four turbines with a rated 150 in² opening each and eight soffit vents rated at 50 in² apiece.
Worked calculation
The exhaust group has 600 in², while intake has 400 in². For the 720 in² intake target, the 320 in² shortfall takes seven more 50 in² units.
Change the inputs to test your own measurements. Reset restores this example.
Results
LiveCorrect the highlighted inputs to update your results.
- Required total NFA
- Target per vent group
- Installed low intake
- Installed high exhaust
- Installed total NFA
- Balanced NFA equivalent
- Upper share of installed NFA
- Intake shortfall
- Exhaust shortfall
- Total soffit vent units needed
- Total high exhaust units needed
- Additional soffit units
- Additional high exhaust units
- High exhaust exceeds the low intake NFA. Add or clear low intake before relying on the exhaust rating.
- One or both vent groups are below the 50/50 planning target.
Worksheet inputs US customary
- Vented attic floor area
- 1,500 ft²
- Ventilation ratio
- 1:150 · baseline
- Soffit vent units
- 8
- Net free area per soffit vent
- 50 in²
- Exhaust system
- Turbine vents
- Exhaust vents installed or planned
- 4
- Net free area per exhaust vent
- 150 in²
Apply this example to your roof
Use the 1:300 ratio only where the adopted code permits it. Placement and applicable vapor-retarder conditions matter. Confirm unobstructed intake pathways, the specified upper-vent distribution and the vent assembly ratings.
Frequently asked questions
Will adding a fifth turbine fix this attic’s intake shortfall?
Increase or clear low intake first. An additional turbine increases the high exhaust rating while the low intake gap stays at 320 in².
Which turbine rating belongs in an NFA estimate?
Use the documented net free area for the vent assembly. A powered airflow or CFM rating measures something different.