Blower-Door ACH50, Infiltration & ERV Sizing Calculator

Convert a 50 Pa blower-door test into ACH50, approximate natural infiltration and estimate the continuous whole-home ERV or HRV airflow target.

Building and test
ft²
ft³
cfm

20 is a starting assumption. A smaller N-factor estimates more natural infiltration.

°F
Continuous ventilation

Use 0 for the standard bedroom-based assumption.

Air changes at 50 Pa (ACH50)
4 h⁻¹
Estimated natural ACH
0.2 h⁻¹
Continuous ERV / HRV target
84 cfm

The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.

Blower-door airtightness

ACH50 gauge4 h⁻¹ at 50 Pa. Estimated natural rate is 0.2 h⁻¹. Airtightness at 50 Pa02468104 ACH50960 cfm at 50 Pa · N = 20
The scale shows air changes per hour at 50 Pa. It expands when the test result exceeds the original scale.
Measured or inferred flow at 50 Pa
960 cfm
Estimated natural airflow
48 cfm
Estimated infiltration heating load
2,851 Btu/h
Assumed people for sizing
4
Download

How this calculation works

ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.

Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.

The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.

The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.

References

Frequently asked questions

Why is blower-door ACH50 higher than natural ACH?

A blower door deliberately creates 50 Pa of pressure difference. Natural leakage is driven by smaller, variable pressures from weather and stack effect. The N-factor provides a rough conversion.

How do I compare the airflow target with an ERV data sheet?

Check balanced outdoor air delivered at the design external static pressure, then measure actual supply and exhaust after installation. Nominal fan capacity is often given at a different pressure.