Blower-Door ACH50, Infiltration & ERV Sizing Calculator
Convert a 50 Pa blower-door test into ACH50, approximate natural infiltration and estimate the continuous whole-home ERV or HRV airflow target.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Air changes at 50 Pa (ACH50)
- h⁻¹
- Estimated natural ACH
- h⁻¹
- Continuous ERV / HRV target
- cfm
The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.
Blower-door airtightness
- Measured or inferred flow at 50 Pa
- cfm
- Estimated natural airflow
- cfm
- Estimated infiltration heating load
- Btu/h
- Assumed people for sizing
Inputs used
- Conditioned floor area
- 1,800 ft²
- Conditioned interior volume
- 14,400 ft³
- Blower-door reading
- Flow at 50 Pa
- Blower-door airflow at 50 Pa
- 960 cfm
- Climate and shielding N-factor
- 20
- Indoor–outdoor temperature difference
- 55 °F
- Bedrooms
- 3
- Known occupants
- 4
How this calculation works
ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.
Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.
The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.
The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.
References
Frequently asked questions
Why is blower-door ACH50 higher than natural ACH?
A blower door deliberately creates 50 Pa of pressure difference. Natural leakage is driven by smaller, variable pressures from weather and stack effect. The N-factor provides a rough conversion.
How do I compare the airflow target with an ERV data sheet?
Check balanced outdoor air delivered at the design external static pressure, then measure actual supply and exhaust after installation. Nominal fan capacity is often given at a different pressure.