2,500 CFM50 Blower-Door Test in an Old Farmhouse

An auditor records 2,500 cfm at 50 Pa for a 2,300 ft² farmhouse with 18,400 ft³ of conditioned volume. The first sensitivity run uses N = 18 for the exposed site.

Try it Change the N-factor from 18 to 25 without touching the blower-door reading. Compare estimated natural airflow and infiltration heating load.

Building and test
ft²
ft³
cfm

20 is a starting assumption. A smaller N-factor estimates more natural infiltration.

°F
Continuous ventilation

Use 0 for the standard bedroom-based assumption.

Air changes at 50 Pa (ACH50)
8.15 h⁻¹
Estimated natural ACH
0.453 h⁻¹
Continuous ERV / HRV target
106.5 cfm

The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.

Blower-door airtightness

ACH50 gauge8.15 h⁻¹ at 50 Pa. Estimated natural rate is 0.453 h⁻¹. Airtightness at 50 Pa02468108.15 ACH502,500 cfm at 50 Pa · N = 18
The scale shows air changes per hour at 50 Pa. It expands when the test result exceeds the original scale.
Measured or inferred flow at 50 Pa
2,500 cfm
Estimated natural airflow
138.9 cfm
Estimated infiltration heating load
9,450 Btu/h
Assumed people for sizing
5
Download

How this calculation works

ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.

Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.

The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.

The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.

References

Frequently asked questions

Why is the farmhouse airflow target 106.5 cfm despite high leakage?

The shown gross rate comes from floor area and assumed occupancy. The natural leakage estimate is separate from any formal ventilation credit.

What happens when the farmhouse N-factor increases?

The same measured ACH50 is divided by a larger number. Estimated natural leakage and sensible heating load decrease.