Worked example
Eight Occupants in a Five-Bedroom Home
A multigenerational household has eight known occupants, five bedrooms and 2,700 ft² of conditioned floor area. The post-weatherization report gives 2.9 ACH50.
Try it Set known occupants to zero to compare the default bedroom assumption. Restore eight for the higher-occupancy airflow target.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Air changes at 50 Pa (ACH50)
- h⁻¹
- Estimated natural ACH
- h⁻¹
- Continuous ERV / HRV target
- cfm
The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.
Blower-door airtightness
- Measured or inferred flow at 50 Pa
- cfm
- Estimated natural airflow
- cfm
- Estimated infiltration heating load
- Btu/h
- Assumed people for sizing
Inputs used
- Conditioned floor area
- 2,700 ft²
- Conditioned interior volume
- 21,600 ft³
- Blower-door reading
- ACH at 50 Pa
- Blower-door air changes at 50 Pa
- 2.9 h⁻¹
- Climate and shielding N-factor
- 20
- Indoor–outdoor temperature difference
- 55 °F
- Bedrooms
- 5
- Known occupants
- 8
How this calculation works
ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.
Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.
The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.
The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.
References
Frequently asked questions
How much ventilation do the two extra assumed occupants add?
Five bedrooms imply six people in the base calculation. The two additional known residents add 15 cfm to the target.
Should my ERV’s boost setting serve as the baseline in the busy house?
Use delivered airflow at the normal setting and design pressure when comparing with a continuous target. Boost operation is useful for separate peak needs.