Blower-Door Volume with a Conditioned Basement

A home’s conditioned basement sits inside the tested air barrier. Including it yields 3,000 ft² and 24,000 ft³. The blower door measures 1,200 cfm at 50 Pa.

Try it Try the upstairs-only volume while leaving CFM50 fixed. The jump in reported ACH50 illustrates why the test boundary matters.

Building and test
ft²
ft³
cfm

20 is a starting assumption. A smaller N-factor estimates more natural infiltration.

°F
Continuous ventilation

Use 0 for the standard bedroom-based assumption.

Air changes at 50 Pa (ACH50)
3 h⁻¹
Estimated natural ACH
0.158 h⁻¹
Continuous ERV / HRV target
127.5 cfm

The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.

Blower-door airtightness

ACH50 gauge3 h⁻¹ at 50 Pa. Estimated natural rate is 0.158 h⁻¹. Airtightness at 50 Pa02468103 ACH501,200 cfm at 50 Pa · N = 19
The scale shows air changes per hour at 50 Pa. It expands when the test result exceeds the original scale.
Measured or inferred flow at 50 Pa
1,200 cfm
Estimated natural airflow
63.2 cfm
Estimated infiltration heating load
3,752 Btu/h
Assumed people for sizing
5
Download

How this calculation works

ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.

Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.

The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.

The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.

References

Frequently asked questions

Which basement volume belongs in this ACH50 conversion?

Use the conditioned air volume actually inside the tested enclosure. Exclude separated unconditioned rooms even if they are under the same roof.

Why is conditioned floor area entered separately from blower-door volume?

ACH50 uses volume. The gross ventilation target uses floor area and occupancy. Depth, ceiling height and test boundaries can affect those inputs differently.