Ventilation Sizing for a 520 ft² Studio

A small studio has no separate bedroom, a conditioned volume of 4,680 ft³ and a 225 cfm blower-door reading. The project is screening continuous airflow under the bedroom-based formula.

Try it Raise known occupancy to three and compare the result. Compare a manufacturer’s low-speed airflow with the target at the planned duct pressure.

Building and test
ft²
ft³
cfm

20 is a starting assumption. A smaller N-factor estimates more natural infiltration.

°F
Continuous ventilation

Use 0 for the standard bedroom-based assumption.

Air changes at 50 Pa (ACH50)
2.88 h⁻¹
Estimated natural ACH
0.144 h⁻¹
Continuous ERV / HRV target
30.6 cfm

The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.

Blower-door airtightness

ACH50 gauge2.88 h⁻¹ at 50 Pa. Estimated natural rate is 0.144 h⁻¹. Airtightness at 50 Pa02468102.88 ACH50225 cfm at 50 Pa · N = 20
The scale shows air changes per hour at 50 Pa. It expands when the test result exceeds the original scale.
Measured or inferred flow at 50 Pa
225 cfm
Estimated natural airflow
11.2 cfm
Estimated infiltration heating load
668 Btu/h
Assumed people for sizing
2
Download

How this calculation works

ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.

Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.

The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.

The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.

References

Frequently asked questions

Why does a zero-bedroom studio use two assumed people in this calculation?

The bedroom term uses a minimum of one bedroom and then adds one. One known resident leaves that base assumption in place.

Would a larger ceiling height change the studio’s ventilation target?

It changes volume and therefore ACH50 from the same blower-door airflow. The gross ventilation formula uses floor area and assumed occupancy.