Post-Retrofit Airtightness at 515 CFM50

A deep retrofit of a 1,720 ft² house measures 515 cfm at 50 Pa. With 15,480 ft³ of conditioned volume, the auditor compares N-factor assumptions and a 60°F temperature difference.

Try it Run N = 16 and N = 24. Record a range of natural airflow and heat-load estimates while keeping the blower-door measurement fixed.

Building and test
ft²
ft³
cfm

20 is a starting assumption. A smaller N-factor estimates more natural infiltration.

°F
Continuous ventilation

Use 0 for the standard bedroom-based assumption.

Air changes at 50 Pa (ACH50)
2 h⁻¹
Estimated natural ACH
0.125 h⁻¹
Continuous ERV / HRV target
81.6 cfm

The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.

Blower-door airtightness

ACH50 gauge2 h⁻¹ at 50 Pa. Estimated natural rate is 0.125 h⁻¹. Airtightness at 50 Pa02468102 ACH50515 cfm at 50 Pa · N = 16
The scale shows air changes per hour at 50 Pa. It expands when the test result exceeds the original scale.
Measured or inferred flow at 50 Pa
515 cfm
Estimated natural airflow
32.2 cfm
Estimated infiltration heating load
2,086 Btu/h
Assumed people for sizing
4
Download

How this calculation works

ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.

Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.

The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.

The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.

References

Frequently asked questions

Why does the tight retrofit case show different loads for the same test result?

The blower door measures leakage at controlled pressure. Different N-factors represent different assumptions about how weather and the site drive natural leakage.

What should go into a peak heating design beyond this retrofit leakage estimate?

Use room-by-room design conditions and a load method suited to the project. Include envelope heat transfer, design airflow and relevant ventilation recovery.