Worked example
Townhouse Ventilation from an Entered 2.4 ACH50
A townhouse report gives just 2.4 ACH50 for 11,840 ft³ of conditioned volume. The owner uses the ACH input and wants a first-pass balanced ventilation target.
Try it Switch input method to airflow and enter the inferred CFM50 from the results. Verify that both methods give the same ACH50 for the same volume.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Air changes at 50 Pa (ACH50)
- h⁻¹
- Estimated natural ACH
- h⁻¹
- Continuous ERV / HRV target
- cfm
The ASHRAE 62.2 base airflow is shown before applicable credits. The natural airflow is a separate screening estimate.
Blower-door airtightness
- Measured or inferred flow at 50 Pa
- cfm
- Estimated natural airflow
- cfm
- Estimated infiltration heating load
- Btu/h
- Assumed people for sizing
Inputs used
- Conditioned floor area
- 1,480 ft²
- Conditioned interior volume
- 11,840 ft³
- Blower-door reading
- ACH at 50 Pa
- Blower-door air changes at 50 Pa
- 2.4 h⁻¹
- Climate and shielding N-factor
- 23
- Indoor–outdoor temperature difference
- 55 °F
- Bedrooms
- 2
- Known occupants
- 3
How this calculation works
ACH50 = 60 × CFM50 ÷ conditioned volume in cubic feet. Divide ACH50 by the chosen N-factor to estimate natural ACH. The N-factor approximates how climate, wind shielding and height affect infiltration.
Convert natural ACH to airflow using the same volume. Sensible load is approximately 1.08 × natural airflow in cfm × the temperature difference in °F at standard air density. This combines heuristic average leakage with the selected temperature difference.
The gross continuous ASHRAE 62.2 base airflow uses 0.03 cfm per square foot plus 7.5 cfm per assumed person. Assume at least two people, bedrooms plus one, or a higher known occupancy. Metric mode converts this same result to L/s.
The airflow is a selection target before any applicable infiltration or filtration credits. Verify the adopted edition, local requirements, outdoor-air delivery and duct pressure when selecting and commissioning equipment.
References
Frequently asked questions
Why can a townhouse blower-door test include leakage to a neighboring unit?
An unguarded test measures all pathways across the test boundary, including common walls. Air reaching adjacent units may differ from outdoor infiltration.
How do I recover CFM50 from the townhouse report?
Multiply 2.4 by the conditioned volume and divide by 60 minutes per hour. With 11,840 ft³, that gives 473.6 cfm.