Worked example
High Electricity Prices with Low-Cost Natural Gas
A home pays $0.34/kWh for electricity and $0.96/therm for natural gas. The furnace is 96% AFUE and the contractor’s heat pump COP runs from 1.8 to 4.3 over the modeled temperatures.
Try it Reduce the electricity rate toward an off-peak tariff to see when a crossover enters the chart interval.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Heat pump bill savings / year
- USD
- Break-even COP vs. natural gas
- CO₂ reduction / year
- kg CO₂
The modeled heat pump costs more per year than the selected baseline fuel.
Heating cost crossover
- Load-weighted seasonal COP
- Heat pump electricity (kWh/year)
- Heat pump bill / year
- USD
- Heat pump CO₂ / year
- kg CO₂
- Heat pump cost at 5 °F
- $/MMBtu
- Heat pump cost at 17 °F
- $/MMBtu
- Heat pump cost at 47 °F
- $/MMBtu
Fossil fuel comparison
Natural gas Baseline
- Delivered heat price
- 10 $/MMBtu
- Break-even COP
- 9.96
- Crossover temperature
- Outside chart range
- Bill / year
- 620 USD
- CO₂ / year
- 3,427 kg CO₂
Propane
- Delivered heat price
- 32.8 $/MMBtu
- Break-even COP
- 3.04
- Crossover temperature
- 19.9 °F
- Bill / year
- 2,033.85 USD
- CO₂ / year
- 4,331 kg CO₂
Heating oil
- Delivered heat price
- 30.58 $/MMBtu
- Break-even COP
- 3.26
- Crossover temperature
- 24.7 °F
- Bill / year
- 1,895.94 USD
- CO₂ / year
- 5,395 kg CO₂
Inputs used
- Electricity rate
- 0.34 $/kWh
- Natural gas rate
- 0.96 $/therm
- Propane rate
- 2.7 $/US gal
- Heating oil rate
- 3.6 $/US gal
- Gas appliance AFUE
- 96 %
- Propane appliance AFUE
- 90 %
- Oil appliance AFUE
- 85 %
- COP at 47°F
- 4.3
- COP at 17°F
- 2.9
- COP at 5°F
- 1.8
- Baseline fuel
- Natural gas
- Annual delivered heat
- 62 MMBtu
- Share of heat at 47°F
- 55 %
- Share of heat at 17°F
- 35 %
- Share of heat at 5°F
- 10 %
- Electric grid CO₂ intensity
- 0.38 kg CO₂/kWh
How this calculation works
Heat pump cost per delivered MMBtu equals 293.071 × electricity price ÷ COP. Fuel cost per delivered MMBtu is the retail price divided by fuel heat content and AFUE. The crossover COP is the electricity-price numerator divided by the fuel’s delivered heat price.
The seasonal COP is the delivered-heat-weighted harmonic mean of the three entered COPs. Bin percentages describe heat output, so a colder bin can represent a larger share of heating than of hours.
Fuel heat content uses 0.100 MMBtu per therm, 0.091452 MMBtu per US gallon of propane and 0.1385 MMBtu per US gallon of heating oil. Direct combustion emits 53.06, 62.87 and 73.96 kg CO₂ per MMBtu of fuel input, respectively. Heat pump emissions use the entered electricity factor.
The crossover is economic. Check temperature-specific capacity, defrost, backup heat, utility fixed charges, equipment and distribution losses separately.
References
Frequently asked questions
What does “outside chart range” mean for the low-cost gas case?
The modeled heat pump COP never reaches the break-even target between 5°F and 47°F. The curve ends at the two outer performance anchors.
Can a time-of-use electricity rate move the gas crossover?
Yes. Run separate rates for time windows that coincide with heat demand. A low rate at hours with little demand may have a small annual effect.