Radiant Floor PEX Spacing & Loop Length Calculator
Lay out a heated floor by tubing spacing, tubing size and manifold distance. Estimate total tubing, balanced loops, manifold ports and water flow.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Balanced loops / port pairs
- Total PEX tubing
- ft
- Zone water flow
- US gal/min
The loop count balances equal areas. Check pressure drop, actual routes and the floor’s heat output before selection.
Serpentine loop sketch
- Length per loop with leads
- ft
- Planning limit per loop
- ft
- Active tubing across floor
- ft
- Supply + return lead per loop
- ft
- Water flow per loop
- US gal/min
- Total zone heat load
- Btu/h
Inputs used
- Net heated floor area
- 540 ft²
- Tubing on-center spacing
- 9 in
- Nominal PEX size
- ½ in · 300 ft max
- One-way manifold lead per loop
- 18 ft
- Active tubing allowance
- 5 %
- Design floor heat flux
- 20 Btu/(h·ft²)
- Water supply–return temperature drop
- 10 °F
How this calculation works
Active tubing length is net area ÷ spacing, plus the entered allowance. Add two times the one-way lead to every circuit. Divide active length by the usable length per loop and round up.
Each circuit serves an equal share of the area in this estimate. One supply-and-return port pair is needed per circuit. The planning limits are 300 ft for ½-in PEX and 400 ft for ⅝-in PEX, including leads.
Total water flow in US gallons per minute is load in Btu/h divided by 500.4 times the supply-to-return temperature drop in °F. Glycol concentration, operating temperature, pressure drop, floor output, bend radius and pump selection require project-specific checks.
References
Frequently asked questions
Are the manifold leads included in the 300 ft or 400 ft planning limit?
Yes. Each loop uses the one-way distance twice. The remaining length is available for active tubing inside the heated floor.
How many manifold connections does a four-loop floor need?
Specify four port pairs. That means four supply and four return connections. The flow estimate assumes the four loops share the zone load equally.