720 ft² Slab with ⅝-Inch PEX and Four Loops

A small slab uses 8-inch spacing and a manifold 25 ft from the average loop entry. The installer is screening ⅝-inch PEX against a 400 ft planning cap.

Try it Switch to the ½-inch planning cap without changing spacing. Compare the number of circuits and the footage consumed by leads.

Floor and circuit geometry
ft²
ft

Supply and return leads both count toward the loop limit.

%

Add a margin for bends and irregular coverage if required.

Hydronic load
Btu/(h·ft²)
°F
Balanced loops / port pairs
4
Total PEX tubing
1,280 ft
Zone water flow
2.16 US gal/min

The loop count balances equal areas. Check pressure drop, actual routes and the floor’s heat output before selection.

Serpentine loop sketch

Serpentine PEX circuit layout4 balanced loops at 320 ft each. Maximum planned length 400 ft. 8 in on center4 loopsSupply / return manifold320 ft and 0.54 US gal/min per loop
The sketch represents equal-area circuits and paired leads. Use a scaled plan for route placement and bend geometry.
Length per loop with leads
320 ft
Planning limit per loop
400 ft
Active tubing across floor
1,080 ft
Supply + return lead per loop
50 ft
Water flow per loop
0.54 US gal/min
Total zone heat load
12,960 Btu/h
Download

How this calculation works

Active tubing length is net area ÷ spacing, plus the entered allowance. Add two times the one-way lead to every circuit. Divide active length by the usable length per loop and round up.

Each circuit serves an equal share of the area in this estimate. One supply-and-return port pair is needed per circuit. The planning limits are 300 ft for ½-in PEX and 400 ft for ⅝-in PEX, including leads.

Total water flow in US gallons per minute is load in Btu/h divided by 500.4 times the supply-to-return temperature drop in °F. Glycol concentration, operating temperature, pressure drop, floor output, bend radius and pump selection require project-specific checks.

References

Frequently asked questions

Why does the 720 ft² slab need four circuits with a 400 ft cap?

Each circuit spends 50 ft on leads, leaving 350 ft active. Three circuits leave room for just 1,050 ft, while the slab needs 1,080 ft active.

Is an equal 320 ft circuit length mandatory in this slab?

It is a planning target for equal area and load. Adjust actual routes to room geometry and balance to the needed flow per circuit.