Worked example
An Irregular Kitchen with an 8% Tubing Allowance
The radiant zone in a kitchen and family room has 460 ft² of heatable floor after excluding permanent cabinets. The estimate uses 9-inch spacing and 11 ft one-way manifold runs.
Try it Remove the allowance and compare length. Re-enter it after the comparison, then use a scaled plan to check the islands and irregular room edges.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Balanced loops / port pairs
- Total PEX tubing
- ft
- Zone water flow
- US gal/min
The loop count balances equal areas. Check pressure drop, actual routes and the floor’s heat output before selection.
Serpentine loop sketch
- Length per loop with leads
- ft
- Planning limit per loop
- ft
- Active tubing across floor
- ft
- Supply + return lead per loop
- ft
- Water flow per loop
- US gal/min
- Total zone heat load
- Btu/h
Inputs used
- Net heated floor area
- 460 ft²
- Tubing on-center spacing
- 9 in
- Nominal PEX size
- ½ in · 300 ft max
- One-way manifold lead per loop
- 11 ft
- Active tubing allowance
- 8 %
- Design floor heat flux
- 24 Btu/(h·ft²)
- Water supply–return temperature drop
- 10 °F
How this calculation works
Active tubing length is net area ÷ spacing, plus the entered allowance. Add two times the one-way lead to every circuit. Divide active length by the usable length per loop and round up.
Each circuit serves an equal share of the area in this estimate. One supply-and-return port pair is needed per circuit. The planning limits are 300 ft for ½-in PEX and 400 ft for ⅝-in PEX, including leads.
Total water flow in US gallons per minute is load in Btu/h divided by 500.4 times the supply-to-return temperature drop in °F. Glycol concentration, operating temperature, pressure drop, floor output, bend radius and pump selection require project-specific checks.
References
Frequently asked questions
Should the kitchen area include cabinetry and the island?
Enter the floor area where tubing will actually be installed. Keep permanent obstructions out of the active area when they are omitted in the design.
Why apply the 8% allowance to active tube length only?
The allowance accounts for floor coverage and routing. The separately entered manifold leads represent their own measured length.