Worked example
1,200 ft² Workshop with 12-Inch Radiant Spacing
A workshop slab has a low estimated heat flux and uses 12-inch tubing centers. Four planned ⅝-inch circuits each reach the manifold by a 15 ft lead.
Try it Increase the load from 15 to 22 Btu/h·ft² without editing area or spacing. Review the new total and per-circuit flow requirements.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Balanced loops / port pairs
- Total PEX tubing
- ft
- Zone water flow
- US gal/min
The loop count balances equal areas. Check pressure drop, actual routes and the floor’s heat output before selection.
Serpentine loop sketch
- Length per loop with leads
- ft
- Planning limit per loop
- ft
- Active tubing across floor
- ft
- Supply + return lead per loop
- ft
- Water flow per loop
- US gal/min
- Total zone heat load
- Btu/h
Inputs used
- Net heated floor area
- 1,200 ft²
- Tubing on-center spacing
- 12 in
- Nominal PEX size
- ⅝ in · 400 ft max
- One-way manifold lead per loop
- 15 ft
- Active tubing allowance
- 0 %
- Design floor heat flux
- 15 Btu/(h·ft²)
- Water supply–return temperature drop
- 15 °F
How this calculation works
Active tubing length is net area ÷ spacing, plus the entered allowance. Add two times the one-way lead to every circuit. Divide active length by the usable length per loop and round up.
Each circuit serves an equal share of the area in this estimate. One supply-and-return port pair is needed per circuit. The planning limits are 300 ft for ½-in PEX and 400 ft for ⅝-in PEX, including leads.
Total water flow in US gallons per minute is load in Btu/h divided by 500.4 times the supply-to-return temperature drop in °F. Glycol concentration, operating temperature, pressure drop, floor output, bend radius and pump selection require project-specific checks.
References
Frequently asked questions
Why can the workshop use wider spacing in this planning example?
The assumed design demand is relatively low. Assess the actual floor construction and required fluid temperatures before deciding whether wide spacing delivers enough heat.
How many manifold ports does the workshop sketch represent?
Four supply-and-return pairs serve the four circuits. The sizing calculation divides the total flow equally for a first estimate.