Three ½-Inch PEX Loops in a 350 ft² Basement

A radiant retrofit has 350 ft² of active floor, a nearby manifold and 6-inch tubing spacing. Supply and return each travel 10 ft per circuit before reaching the active floor.

Try it Switch spacing from six to nine inches to see how active length and loop count change. Compare against the room load before choosing a layout.

Floor and circuit geometry
ft²
ft

Supply and return leads both count toward the loop limit.

%

Add a margin for bends and irregular coverage if required.

Hydronic load
Btu/(h·ft²)
°F
Balanced loops / port pairs
3
Total PEX tubing
760 ft
Zone water flow
1.54 US gal/min

The loop count balances equal areas. Check pressure drop, actual routes and the floor’s heat output before selection.

Serpentine loop sketch

Serpentine PEX circuit layout3 balanced loops at 253.33 ft each. Maximum planned length 300 ft. 6 in on center3 loopsSupply / return manifold253.3 ft and 0.51 US gal/min per loop
The sketch represents equal-area circuits and paired leads. Use a scaled plan for route placement and bend geometry.
Length per loop with leads
253.33 ft
Planning limit per loop
300 ft
Active tubing across floor
700 ft
Supply + return lead per loop
20 ft
Water flow per loop
0.51 US gal/min
Total zone heat load
7,700 Btu/h
Download

How this calculation works

Active tubing length is net area ÷ spacing, plus the entered allowance. Add two times the one-way lead to every circuit. Divide active length by the usable length per loop and round up.

Each circuit serves an equal share of the area in this estimate. One supply-and-return port pair is needed per circuit. The planning limits are 300 ft for ½-in PEX and 400 ft for ⅝-in PEX, including leads.

Total water flow in US gallons per minute is load in Btu/h divided by 500.4 times the supply-to-return temperature drop in °F. Glycol concentration, operating temperature, pressure drop, floor output, bend radius and pump selection require project-specific checks.

References

Frequently asked questions

How is the basement’s 700 ft of active PEX length estimated?

Six-inch spacing corresponds to 2 ft of active tube per square foot. Multiply 350 by 2, then add 20 ft of paired leads for each circuit.

Can a basement with the same area use fewer circuits?

A wider spacing, shorter leads or larger suitable tubing can lower the count. Verify floor heat output and hydraulic pressure drop before selecting the layout.