Worked example
Three ½-Inch PEX Loops in a 350 ft² Basement
A radiant retrofit has 350 ft² of active floor, a nearby manifold and 6-inch tubing spacing. Supply and return each travel 10 ft per circuit before reaching the active floor.
Try it Switch spacing from six to nine inches to see how active length and loop count change. Compare against the room load before choosing a layout.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Balanced loops / port pairs
- Total PEX tubing
- ft
- Zone water flow
- US gal/min
The loop count balances equal areas. Check pressure drop, actual routes and the floor’s heat output before selection.
Serpentine loop sketch
- Length per loop with leads
- ft
- Planning limit per loop
- ft
- Active tubing across floor
- ft
- Supply + return lead per loop
- ft
- Water flow per loop
- US gal/min
- Total zone heat load
- Btu/h
Inputs used
- Net heated floor area
- 350 ft²
- Tubing on-center spacing
- 6 in
- Nominal PEX size
- ½ in · 300 ft max
- One-way manifold lead per loop
- 10 ft
- Active tubing allowance
- 0 %
- Design floor heat flux
- 22 Btu/(h·ft²)
- Water supply–return temperature drop
- 10 °F
How this calculation works
Active tubing length is net area ÷ spacing, plus the entered allowance. Add two times the one-way lead to every circuit. Divide active length by the usable length per loop and round up.
Each circuit serves an equal share of the area in this estimate. One supply-and-return port pair is needed per circuit. The planning limits are 300 ft for ½-in PEX and 400 ft for ⅝-in PEX, including leads.
Total water flow in US gallons per minute is load in Btu/h divided by 500.4 times the supply-to-return temperature drop in °F. Glycol concentration, operating temperature, pressure drop, floor output, bend radius and pump selection require project-specific checks.
References
Frequently asked questions
How is the basement’s 700 ft of active PEX length estimated?
Six-inch spacing corresponds to 2 ft of active tube per square foot. Multiply 350 by 2, then add 20 ft of paired leads for each circuit.
Can a basement with the same area use fewer circuits?
A wider spacing, shorter leads or larger suitable tubing can lower the count. Verify floor heat output and hydraulic pressure drop before selecting the layout.