Worked example
A 90 ft² Tile Mudroom with One PEX Circuit
A 90 ft² mudroom uses 6-inch spacing to screen a high load near an exterior door. The manifold is about 20 ft away, and the installer includes a 5% active length allowance.
Try it Change the water temperature drop from 10°F to 15°F. The flow target changes while the layout length stays the same.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Balanced loops / port pairs
- Total PEX tubing
- ft
- Zone water flow
- US gal/min
The loop count balances equal areas. Check pressure drop, actual routes and the floor’s heat output before selection.
Serpentine loop sketch
- Length per loop with leads
- ft
- Planning limit per loop
- ft
- Active tubing across floor
- ft
- Supply + return lead per loop
- ft
- Water flow per loop
- US gal/min
- Total zone heat load
- Btu/h
Inputs used
- Net heated floor area
- 90 ft²
- Tubing on-center spacing
- 6 in
- Nominal PEX size
- ½ in · 300 ft max
- One-way manifold lead per loop
- 20 ft
- Active tubing allowance
- 5 %
- Design floor heat flux
- 30 Btu/(h·ft²)
- Water supply–return temperature drop
- 10 °F
How this calculation works
Active tubing length is net area ÷ spacing, plus the entered allowance. Add two times the one-way lead to every circuit. Divide active length by the usable length per loop and round up.
Each circuit serves an equal share of the area in this estimate. One supply-and-return port pair is needed per circuit. The planning limits are 300 ft for ½-in PEX and 400 ft for ⅝-in PEX, including leads.
Total water flow in US gallons per minute is load in Btu/h divided by 500.4 times the supply-to-return temperature drop in °F. Glycol concentration, operating temperature, pressure drop, floor output, bend radius and pump selection require project-specific checks.
References
Frequently asked questions
What part of the mudroom tubing estimate is outside the room?
The two 20 ft manifold leads contribute 40 ft to total length. The remaining estimated 189 ft covers the floor and the layout allowance.
Why should floor surface temperature be checked in the tiled mudroom?
The heat flux input describes room demand. The floor finish, tube depth, water temperature and comfort limits determine how much heat the assembly delivers.