Wall R-Value & Thermal Bridging Calculator

Estimate the effective R-value and U-factor of a wall or ceiling. Compare the insulated cavity with the path through the framing and see what continuous insulation changes.

Framing and insulation
R

Use the R-value at the actual cavity depth.

Continuous layers
in

Use 0 for an assembly without continuous foam.

R/in

Use 0 for material defaults (polyiso 5.7, XPS 5.0, EPS 3.8 R/in).

R
R
R
R
Effective assembly R
23.01 R
Assembly U-factor
0.043 Btu/(h·ft²·°F)
R lost to framing
19.6 %

Compare the framing area fraction with the share of heat that goes through framing.

Assembly cross-section

Cavity and framing heat flow25% framing · 39.7% of heat through framing. Effective resistance 23.01 R. Continuous foam 5.7 R. IndoorsOutdoorsInsulated cavityWood framingExterior foam25% framing · 39.7% of heat through framing
Layer widths and framing bands show the relative geometry of the model. The arrows follow the cavity and framing heat-flow paths.
Nominal cavity-path R
28.62 R
Framing-path R
14.5 R
Continuous foam R
5.7 R
Framing area fraction
25 %
Heat through framing
39.7 %
Download

How this calculation works

Add the interior film, finish, sheathing, exterior film and continuous insulation to both paths. Add installed cavity R to the cavity path and framing-layer R to the stud path. Wood framing uses 1.25 R per inch of depth.

Weight the two conductances by area using U = (1 − f) ÷ R_cavity + f ÷ R_framing. Effective R = 1 ÷ U. The percentage loss compares effective R to the full cavity-path R. It can be negative when the framing layer has more resistance than the cavity fill.

Spacing presets assume 25% and 22% framing in walls, and 12% and 9% in ceilings, at 16 and 24 inches on center. Measure the fraction for a project takeoff. Foam ratings are starting assumptions. Use the product’s rating at representative temperatures.

Steel spreads heat sideways through the flanges. Its editable equivalent path resistance makes this a screening comparison. For steel design or documented compliance, use tested assembly data, a zone method or a validated thermal model.

References

Frequently asked questions

Why is assembly R lower than the insulation label?

The label describes the insulation itself. Framing often conducts heat faster than the cavity fill. The assembly result weights the conductance of each path by its area and then inverts the total.

Where do continuous foam and air films go in a parallel-path wall model?

Continuous layers are in series with each path. Add their resistances once to the framing path and once to the cavity path before calculating the two conductances.