Worked example
R-13 in a 2×4 Bungalow Wall
An auditor opens a 1950s bungalow wall during a kitchen renovation. The framing is 2×4 at 16 inches on center with an R-13 cavity batt and no exterior rigid insulation.
Try it Compare the cavity-path R with effective R. Then add an inch of EPS to see how much the same foam layer improves the stud path.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Effective assembly R
- R
- Assembly U-factor
- Btu/(h·ft²·°F)
- R lost to framing
- %
Compare the framing area fraction with the share of heat that goes through framing.
Assembly cross-section
- Nominal cavity-path R
- R
- Framing-path R
- R
- Continuous foam R
- R
- Framing area fraction
- %
- Heat through framing
- %
Inputs used
- Assembly
- Wall
- Framing material
- Wood
- Nominal framing depth
- 2 × 4 (3½ in)
- On-center spacing
- 16 in
- Framing fraction source
- Spacing estimate
- Installed cavity insulation R
- 13 R
- Exterior rigid foam
- EPS
- Continuous foam thickness
- 0 in
- Project foam R per thickness
- 0 R/in
- Interior air film R
- 0.68 R
- Interior finish R
- 0.45 R
- Sheathing and other layers R
- 0.62 R
- Exterior air film R
- 0.17 R
How this calculation works
Add the interior film, finish, sheathing, exterior film and continuous insulation to both paths. Add installed cavity R to the cavity path and framing-layer R to the stud path. Wood framing uses 1.25 R per inch of depth.
Weight the two conductances by area using U = (1 − f) ÷ R_cavity + f ÷ R_framing. Effective R = 1 ÷ U. The percentage loss compares effective R to the full cavity-path R. It can be negative when the framing layer has more resistance than the cavity fill.
Spacing presets assume 25% and 22% framing in walls, and 12% and 9% in ceilings, at 16 and 24 inches on center. Measure the fraction for a project takeoff. Foam ratings are starting assumptions. Use the product’s rating at representative temperatures.
Steel spreads heat sideways through the flanges. Its editable equivalent path resistance makes this a screening comparison. For steel design or documented compliance, use tested assembly data, a zone method or a validated thermal model.
References
Frequently asked questions
Why does the R-13 bungalow batt yield less than R-13 overall?
Old studs, plates and headers offer less resistance than the batt. With the default 25% framing fraction, their higher conductance more than offsets the small added resistance of finishes and films.
What should I enter for a bungalow wall with partial empty bays?
Use a separate run for the empty bays or derive a cavity-path conductance weighted by the measured areas. An arithmetic average of cavity R can understate heat loss.