Worked example
R-30 Garage Ceiling Under a Bedroom
An auditor models a bedroom floor above an unconditioned garage using the ceiling framing preset. The 2×8 joists are at 16 inches on center. The example assumes R-30 at the installed depth and uses an edited interior film resistance of R-0.61.
Try it Switch to a measured framing fraction if your section includes doubled joists or a beam. Watch how added framing changes the ceiling result.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Effective assembly R
- R
- Assembly U-factor
- Btu/(h·ft²·°F)
- R lost to framing
- %
Compare the framing area fraction with the share of heat that goes through framing.
Assembly cross-section
- Nominal cavity-path R
- R
- Framing-path R
- R
- Continuous foam R
- R
- Framing area fraction
- %
- Heat through framing
- %
Inputs used
- Assembly
- Ceiling
- Framing material
- Wood
- Nominal framing depth
- 2 × 8 (7¼ in)
- On-center spacing
- 16 in
- Framing fraction source
- Spacing estimate
- Installed cavity insulation R
- 30 R
- Exterior rigid foam
- Polyiso
- Continuous foam thickness
- 0 in
- Project foam R per thickness
- 0 R/in
- Interior air film R
- 0.61 R
- Interior finish R
- 0.45 R
- Sheathing and other layers R
- 0.62 R
- Exterior air film R
- 0.17 R
How this calculation works
Add the interior film, finish, sheathing, exterior film and continuous insulation to both paths. Add installed cavity R to the cavity path and framing-layer R to the stud path. Wood framing uses 1.25 R per inch of depth.
Weight the two conductances by area using U = (1 − f) ÷ R_cavity + f ÷ R_framing. Effective R = 1 ÷ U. The percentage loss compares effective R to the full cavity-path R. It can be negative when the framing layer has more resistance than the cavity fill.
Spacing presets assume 25% and 22% framing in walls, and 12% and 9% in ceilings, at 16 and 24 inches on center. Measure the fraction for a project takeoff. Foam ratings are starting assumptions. Use the product’s rating at representative temperatures.
Steel spreads heat sideways through the flanges. Its editable equivalent path resistance makes this a screening comparison. For steel design or documented compliance, use tested assembly data, a zone method or a validated thermal model.
References
Frequently asked questions
Can I enter R-30 when a batt is compressed between the garage ceiling joists?
Use its installed resistance at the actual thickness. Product data can differ substantially between full-loft and compressed applications.
Do garage-ceiling fire separation requirements follow from the R result?
The R result addresses conduction. Confirm the required separation, air barrier and any penetration details for the garage floor assembly separately.