Worked example
Steel-Stud Condo Wall with Continuous XPS
A condo enclosure team compares two inches of exterior XPS against an existing R-15 steel-stud cavity. Their screening inputs use 22% equivalent framing area and an R-1.3 framed-layer path.
Try it Try one and three inches of XPS. Use the results to compare direction and approximate magnitude while arranging a tested or modeled assembly check.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Effective assembly R
- R
- Assembly U-factor
- Btu/(h·ft²·°F)
- R lost to framing
- %
Steel framing uses the entered equivalent path. Confirm the assembly with tested data or a zone model for specification work.
Assembly cross-section
- Nominal cavity-path R
- R
- Framing-path R
- R
- Continuous foam R
- R
- Framing area fraction
- %
- Heat through framing
- %
Inputs used
- Assembly
- Wall
- Framing material
- Steel
- Nominal framing depth
- 2 × 4 (3½ in)
- On-center spacing
- 24 in
- Framing fraction source
- Project value
- Project framing fraction
- 22 %
- Equivalent steel path R
- 1.3 R
- Installed cavity insulation R
- 15 R
- Exterior rigid foam
- XPS
- Continuous foam thickness
- 2 in
- Project foam R per thickness
- 0 R/in
- Interior air film R
- 0.68 R
- Interior finish R
- 0.45 R
- Sheathing and other layers R
- 0.62 R
- Exterior air film R
- 0.17 R
How this calculation works
Add the interior film, finish, sheathing, exterior film and continuous insulation to both paths. Add installed cavity R to the cavity path and framing-layer R to the stud path. Wood framing uses 1.25 R per inch of depth.
Weight the two conductances by area using U = (1 − f) ÷ R_cavity + f ÷ R_framing. Effective R = 1 ÷ U. The percentage loss compares effective R to the full cavity-path R. It can be negative when the framing layer has more resistance than the cavity fill.
Spacing presets assume 25% and 22% framing in walls, and 12% and 9% in ceilings, at 16 and 24 inches on center. Measure the fraction for a project takeoff. Foam ratings are starting assumptions. Use the product’s rating at representative temperatures.
Steel spreads heat sideways through the flanges. Its editable equivalent path resistance makes this a screening comparison. For steel design or documented compliance, use tested assembly data, a zone method or a validated thermal model.
References
Frequently asked questions
Is R-1.3 the material R-value of a steel stud?
It is an assumed equivalent layer resistance for this rough example. Steel flange geometry changes the real heat flow, so obtain tested values or a zone-model result for specification work.
Why does the XPS help both sides of the condo wall comparison?
The continuous foam adds in-series resistance outside the insulated stud bays and the steel heat-flow path. The two paths then differ by less in relative terms.