Worked example
Two and a Half Inches of EPS Under New Siding
A small contractor is pricing siding for a house with R-11 in the existing 2×4 cavities. The estimate adds 2½ inches of EPS and uses R-0.80 for the sheathing and associated layers.
Try it Switch among EPS, XPS and polyiso at the same thickness. Compare the effective R change before checking product-specific properties and cladding attachment.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Effective assembly R
- R
- Assembly U-factor
- Btu/(h·ft²·°F)
- R lost to framing
- %
Compare the framing area fraction with the share of heat that goes through framing.
Assembly cross-section
- Nominal cavity-path R
- R
- Framing-path R
- R
- Continuous foam R
- R
- Framing area fraction
- %
- Heat through framing
- %
Inputs used
- Assembly
- Wall
- Framing material
- Wood
- Nominal framing depth
- 2 × 4 (3½ in)
- On-center spacing
- 16 in
- Framing fraction source
- Spacing estimate
- Installed cavity insulation R
- 11 R
- Exterior rigid foam
- EPS
- Continuous foam thickness
- 2.5 in
- Project foam R per thickness
- 0 R/in
- Interior air film R
- 0.68 R
- Interior finish R
- 0.45 R
- Sheathing and other layers R
- 0.8 R
- Exterior air film R
- 0.17 R
How this calculation works
Add the interior film, finish, sheathing, exterior film and continuous insulation to both paths. Add installed cavity R to the cavity path and framing-layer R to the stud path. Wood framing uses 1.25 R per inch of depth.
Weight the two conductances by area using U = (1 − f) ÷ R_cavity + f ÷ R_framing. Effective R = 1 ÷ U. The percentage loss compares effective R to the full cavity-path R. It can be negative when the framing layer has more resistance than the cavity fill.
Spacing presets assume 25% and 22% framing in walls, and 12% and 9% in ceilings, at 16 and 24 inches on center. Measure the fraction for a project takeoff. Foam ratings are starting assumptions. Use the product’s rating at representative temperatures.
Steel spreads heat sideways through the flanges. Its editable equivalent path resistance makes this a screening comparison. For steel design or documented compliance, use tested assembly data, a zone method or a validated thermal model.
References
Frequently asked questions
How much continuous R does this 2½-inch EPS example assume?
The EPS preset is 3.8 R per inch, so 2½ inches adds R-9.5 to each modeled path. Compare that assumption with the actual product label.
Does changing the siding material require changing the EPS entry?
Adjust the outer layers if their resistance changes. EPS type and thickness can stay put when the board itself stays the same.