Worked example
24-Inch Advanced Framing with a Measured 17% Fraction
A builder estimates 17% framing from elevations for a 24-inch-on-center wall. The wall uses 2×6 members, R-23 cavity insulation and an inch of XPS outside the sheathing.
Try it Compare the measured 17% fraction with the spacing-based 22% wall preset. Leave the other inputs alone so the comparison isolates framing.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Effective assembly R
- R
- Assembly U-factor
- Btu/(h·ft²·°F)
- R lost to framing
- %
Compare the framing area fraction with the share of heat that goes through framing.
Assembly cross-section
- Nominal cavity-path R
- R
- Framing-path R
- R
- Continuous foam R
- R
- Framing area fraction
- %
- Heat through framing
- %
Inputs used
- Assembly
- Wall
- Framing material
- Wood
- Nominal framing depth
- 2 × 6 (5½ in)
- On-center spacing
- 24 in
- Framing fraction source
- Project value
- Project framing fraction
- 17 %
- Installed cavity insulation R
- 23 R
- Exterior rigid foam
- XPS
- Continuous foam thickness
- 1 in
- Project foam R per thickness
- 0 R/in
- Interior air film R
- 0.68 R
- Interior finish R
- 0.45 R
- Sheathing and other layers R
- 0.62 R
- Exterior air film R
- 0.17 R
How this calculation works
Add the interior film, finish, sheathing, exterior film and continuous insulation to both paths. Add installed cavity R to the cavity path and framing-layer R to the stud path. Wood framing uses 1.25 R per inch of depth.
Weight the two conductances by area using U = (1 − f) ÷ R_cavity + f ÷ R_framing. Effective R = 1 ÷ U. The percentage loss compares effective R to the full cavity-path R. It can be negative when the framing layer has more resistance than the cavity fill.
Spacing presets assume 25% and 22% framing in walls, and 12% and 9% in ceilings, at 16 and 24 inches on center. Measure the fraction for a project takeoff. Foam ratings are starting assumptions. Use the product’s rating at representative temperatures.
Steel spreads heat sideways through the flanges. Its editable equivalent path resistance makes this a screening comparison. For steel design or documented compliance, use tested assembly data, a zone method or a validated thermal model.
References
Frequently asked questions
Why does the 24-inch project use 17% instead of the spacing preset?
Framing at openings, corners and floor lines determines the actual area. The example uses the builder’s elevation takeoff for that specific wall.
How should I count a header when measuring the advanced-framing fraction?
Count the header area according to its actual thermal path. A fully solid header and an insulated header may need different areas or a separate run.