WaterTreatLab

Chemical feed / Worked example

Phosphate Feed and 55-Gallon Day Tank

Work out phosphate metering flow, capacity and days of usable stock for a 1.8 MGD process.

Inputs

Process & solution
mg/L
%
Mass percent (w/w)
Pump & inventory
gph
gal
gal

Results

US customary
Liquid feed
0.24414 gph 15.403 mL/min
Active chemical
18.765 lb/d 8.5117 kg/d
Pump capacity used
48.828 %
Day-tank autonomy
9.3867 d
Chemical metering circuitLive diagram
Chemical metering circuitThe day-tank fill shows remaining stock after 24 hours from a full tank. Day-tank autonomy9.3867 dLiquid stock feed0.24414 gphMetering pumpProcess mainRequired pump output48.828 %10%90%
The day-tank fill shows remaining stock after 24 hours from a full tank.
Bulk-tank autonomy
46.933 d
Dose target
1.25 mg/L
Dose at rated flow
2.56 mg/L
Stock used per day
5.8594 gal/d

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. The 1.25 mg/L target gives an active demand of 18.765 lb/day.
  2. At 30% w/w and 1.28 SG, the feed is about 0.24414 gph, or 5.8594 gal/day. The 55 usable gal lasts about 9.39 days.

More worked examples

Hypochlorite Feed at 2 MGD

Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.

Equations & conventions

Active mass rate
W = 8.34 × Qₘɢᴅ × D

Q is US million gallons per day, D is mg/L of active chemical and W is lb/day. The tool uses the EPA operator convention of 8.34 exactly.

Liquid feed rate
q = W / (24 × 8.34 × SG × w)

w is active mass fraction, for example 0.125 at 12.5% w/w. The result is US gal/h. Use the stock-specific SG and the same active chemical basis as the dose target.

Capacity and inventory
Setting = 100q / qᵣₐₜₑ𝒹, autonomy = Vᵤₛₐᵦₗₑ / (24q)

Pump setting is the equivalent share of rated flow. Calibrate stroke and speed at actual pressure. Use liquid inventory above the unusable heel and any reserved stock.

Planning basis

The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.

Questions

Can I mix an as-P dose with a stock labeled as PO₄?

Convert the target and stock to the same active basis before entering them. Product strength can be reported using either mass basis.