Find why a 1 gph pump is oversized for a 0.01236 gph feed target on a small industrial water stream.

Inputs

Process & solution
mg/L
%
Mass percent (w/w)
Pump & inventory
gph
gal
gal

Results

US customary
Liquid feed
0.012363 gph 0.77996 mL/min
Active chemical
1.1259 lb/d 0.5107 kg/d
Pump capacity used
1.2363 %
Day-tank autonomy
33.704 d
Chemical metering circuitLive diagram
Chemical metering circuitThe day-tank fill shows remaining stock after 24 hours from a full tank. Day-tank autonomy33.704 dLiquid stock feed0.012363 gphMetering pumpProcess mainRequired pump output1.2363 %10%90%
The day-tank fill shows remaining stock after 24 hours from a full tank.
Review the operating point
  • Below 10% of rated flow. Check calibrated turndown at operating backpressure.
Bulk-tank autonomy
269.63 d
Dose target
0.9 mg/L
Dose at rated flow
72.8 mg/L
Stock used per day
0.2967 gal/d

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. At 0.15 MGD and 0.9 mg/L, active demand is 1.1259 lb/day.
  2. The concentrated stock needs 0.01236 gph, about 1.24% of the pump’s rated flow.

More worked examples

Hypochlorite Feed at 2 MGD

Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.

Equations & conventions

Active mass rate
W = 8.34 × Qₘɢᴅ × D

Q is US million gallons per day, D is mg/L of active chemical and W is lb/day. The tool uses the EPA operator convention of 8.34 exactly.

Liquid feed rate
q = W / (24 × 8.34 × SG × w)

w is active mass fraction, for example 0.125 at 12.5% w/w. The result is US gal/h. Use the stock-specific SG and the same active chemical basis as the dose target.

Capacity and inventory
Setting = 100q / qᵣₐₜₑ𝒹, autonomy = Vᵤₛₐᵦₗₑ / (24q)

Pump setting is the equivalent share of rated flow. Calibrate stroke and speed at actual pressure. Use liquid inventory above the unusable heel and any reserved stock.

Planning basis

The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.

Questions

Is 1.24% a calibrated stroke position?

It is the required share of rated flow. Check the operating-pressure calibration before choosing the actual stroke and speed.