Hypochlorite Feed at 2 MGD
Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.
Chemical feed / Worked example
Find why a 1 gph pump is oversized for a 0.01236 gph feed target on a small industrial water stream.
For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.
These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.
Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.
Size pump flow for a 0.5% active polymer solution delivering a 0.8 mg/L active dose to 0.75 MGD.
Check liquid coagulant feed at 6 MGD, with a 25 mg/L active target and a 9.5 gph rated metering pump.
Compare a requested 8 mg/L active dose with what an 8 gph pump can meet at peak process flow.
Model a chemical system in standby at zero target dose while the treatment process continues to flow.
Work out phosphate metering flow, capacity and days of usable stock for a 1.8 MGD process.
W = 8.34 × Qₘɢᴅ × DQ is US million gallons per day, D is mg/L of active chemical and W is lb/day. The tool uses the EPA operator convention of 8.34 exactly.
q = W / (24 × 8.34 × SG × w)w is active mass fraction, for example 0.125 at 12.5% w/w. The result is US gal/h. Use the stock-specific SG and the same active chemical basis as the dose target.
Setting = 100q / qᵣₐₜₑ𝒹, autonomy = Vᵤₛₐᵦₗₑ / (24q)Pump setting is the equivalent share of rated flow. Calibrate stroke and speed at actual pressure. Use liquid inventory above the unusable heel and any reserved stock.
The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.
It is the required share of rated flow. Check the operating-pressure calibration before choosing the actual stroke and speed.