WaterTreatLab

Disinfection / Worked example

Ammonia Breakpoint Demand and CT

Calculate the theoretical breakpoint for 1.2 mg/L ammonia-N and keep it separate from outlet residual and chlorine CT.

Inputs

Contact segment
mg/L
gal
gpm
mg·min/L
Breakpoint screen
mg/L as N
mg/L as Cl₂

Results

US customary
Achieved CT
33.6 mg·min/L
Effective time T₁₀
42 min
CT / target
0.74667 ×
Theoretical time T
60 min
Contact basinLive diagram
Contact basinFlow path and effective contact time for the selected baffling class. InletOutlet residualBaffling factor 0.7Theoretical time60 minEffective T₁₀42 minCT / target0.74667 ×
Flow path and effective contact time for the selected baffling class.
Review the operating point
  • Achieved CT is below the entered target at this peak flow and residual.
Breakpoint demand
10.02 mg/L as Cl₂
Dose incl. entered residual
10.82 mg/L as Cl₂

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. Oxidizing 1.2 mg/L ammonia-N consumes a theoretical 9.12 mg/L as Cl₂. The entered other demand brings the screen to 10.02 mg/L.
  2. Adding the entered residual gives 10.82 mg/L as a dose screen. CT still uses the 0.8 mg/L outlet residual and 42 min T₁₀, yielding 33.6 mg·min/L.

More worked examples

Equations & conventions

Theoretical and effective time
T = V / Q, T₁₀ = T × BF

Use operating volume and peak flow for the same segment. EPA Table 4-2 uses 0.1, 0.3, 0.5, 0.7 and 1.0 for progressively improved baffling. Use approved tracer results when available.

Disinfection exposure
CT = C × T₁₀, CT ratio = CT / CTrequired

C is the measured disinfectant residual at the end of the segment. Use the applicable required CT for the disinfectant, organism, inactivation goal, temperature and pH.

Theoretical breakpoint
Dᵦ = 7.6 × ammonia-N + other demand

Express ammonia as N and chlorine as Cl₂. The optional residual allowance is added separately. Determine actual breakpoint from site demand testing and approved operating procedures.

Planning basis

A CT ratio at or above one means the calculated value meets your entered target for this segment. A regulated inactivation determination also requires the governing method, sampling, operating envelope and any segment accounting.

Questions

Why can a breakpoint demand test disagree with 10.02 mg/L?

Reaction products, pH, temperature and other compounds influence real demand. Confirm breakpoint under the actual treatment conditions.