WaterTreatLab

Disinfection / Worked example

Average Baffling at the CT Target

See a 120,000 gal contact basin exactly match a 50 mg·min/L target with average baffling.

Inputs

Contact segment
mg/L
gal
gpm
mg·min/L
Breakpoint screen
mg/L as N
mg/L as Cl₂

Results

US customary
Achieved CT
50 mg·min/L
Effective time T₁₀
40 min
CT / target
1 ×
Theoretical time T
80 min
Contact basinLive diagram
Contact basinFlow path and effective contact time for the selected baffling class. InletOutlet residualBaffling factor 0.5Theoretical time80 minEffective T₁₀40 minCT / target1 ×
Flow path and effective contact time for the selected baffling class.
Breakpoint demand
2.5 mg/L as Cl₂
Dose incl. entered residual
3.75 mg/L as Cl₂

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. Divide volume by flow for 80 min theoretical detention. Average baffling halves that to 40 min.
  2. Multiply 40 min by 1.25 mg/L. Achieved CT is exactly 50 mg·min/L at the inputs.

More worked examples

Equations & conventions

Theoretical and effective time
T = V / Q, T₁₀ = T × BF

Use operating volume and peak flow for the same segment. EPA Table 4-2 uses 0.1, 0.3, 0.5, 0.7 and 1.0 for progressively improved baffling. Use approved tracer results when available.

Disinfection exposure
CT = C × T₁₀, CT ratio = CT / CTrequired

C is the measured disinfectant residual at the end of the segment. Use the applicable required CT for the disinfectant, organism, inactivation goal, temperature and pH.

Theoretical breakpoint
Dᵦ = 7.6 × ammonia-N + other demand

Express ammonia as N and chlorine as Cl₂. The optional residual allowance is added separately. Determine actual breakpoint from site demand testing and approved operating procedures.

Planning basis

A CT ratio at or above one means the calculated value meets your entered target for this segment. A regulated inactivation determination also requires the governing method, sampling, operating envelope and any segment accounting.

Questions

What CT margin remains if the outlet residual falls?

The example starts exactly at its target. Any fall in residual at fixed flow and volume lowers the ratio below one.