WaterTreatLab

Granular filtration / Worked example

Cold-Water Rapid Sand Backwash

Adjust a 20 °C rise-rate reference to 5 °C for a 200 ft² rapid sand filter.

Inputs

Filter cell
ft²
ft
ft
Zero uses the estimate
gal/d
Water backwash
gpm/ft²
°F
min
d⁻¹
Air scour
scfm/ft²
min

Results

US customary
Backwash pump flow
2,604 gpm
Water per wash
26,040 gal
Bed expansion
22.5 %
Daily UBRW
4.3399 %
Filter bed fluidizationLive diagram
Filter bed fluidizationSettled and expanded bed profiles across the filter cell. Settled bed2 ftDuring wash2.45 ftWater flow2,604 gpmExpansion22.5 %Air volume0 scf
Settled and expanded bed profiles across the filter cell.
Actual wash rise rate
13.02 gpm/ft² 31.83 m/h
Equivalent rise rate at 20 °C
15 gpm/ft² 36.671 m/h
Expanded depth
2.45 ft
Daily washwater
26,040 gal/d
Air scour flow
0 scfm
Air volume per scour
0 scf
Water viscosity
1.5012 mPa·s

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. The viscosity correction reduces the 15 gpm/ft² reference to about 13.02 gpm/ft² at 5 °C.
  2. Multiply by 200 ft² for a 2,604 gpm pump rate. Ten minutes consumes about 26,040 gal.

More worked examples

Equations & conventions

Rise rate and washwater
Qwash = A × v, Vwash = Qwash × t

The result is gpm with area in ft² and rise rate in gpm/ft². UBRW is 100 × daily washwater / gross daily production for the same cell.

Temperature adjustment
μ = 0.02414 × 10^(247.8/(Tc + 133.15)), vT = v₂₀ × (μ₂₀/μT)^0.35

μ is an approximate water viscosity in mPa·s. Select whether the input is already at wash temperature or is the reference at 20 °C. The exponent is a planning assumption chosen to approximate seasonal behavior.

Measured bed expansion
Expansion = 100 × (expanded depth / settled depth − 1)

Enter the total operating bed depth during wash. The settled and expanded depths exclude support gravel.

Modeled bed expansion
ε = min(0.80, εref × (v₂₀/vref)^(1/3)); E = 100 × max(0, (1−ε₀)/(1−ε) − 1)

The porosity screen uses ε₀ = 0.40 and εref = 1 − (1 − ε₀)/1.225. The illustrative 20 °C reference rates are 15/17/19 gpm/ft² for sand/dual/anthracite. Use measured depth or a media-specific curve for plant decisions.

Air scour
Air volume = specific standard airflow × A × air time

Report gas volume at the same standard conditions as the entered rate. The 3–5 scfm/ft² Ten States reference applies to underdrain introduction.

Planning basis

The EPA water-wash expansion reference is commonly 20–25% and varies with media and air scour. Verify the bed with a rise measurement or media supplier curve and check trough clearance. The model assumes discrete water and air volumes.

Questions

Why does the model retain the same expansion with colder water?

This case adjusts the wash rate to represent equal fluidization at the new temperature using the stated viscosity proxy.